Sfoglia online o scarica il pdf Istruzioni per per Apparecchiature per serbatoi AQUATECH AquaBreak AB5. AQUATECH AquaBreak AB5 18. Breaktank & pumpset for backflow protection to fluid category 5

 
0.1 
WARNINGS 
0.1.1
Do not touch any live parts for at least 5 minutes after switching off the electricity supply. Failure to 
observe this will constitute a severe Electric shock and/or Burns hazard and may be lethal. 
0.1.2
The equipment is only suitable for earth referenced supplies and must be permanently earthed to 
avoid Electric shock hazard. 
0.1.3
Metal parts (e.g. heat sinks) may reach temperatures of 90 degrees centigrade and will constitute a 
Burns hazard. 
0.1.4
The equipment must not be pressurised beyond the maximum working pressure as stated on 
pumps/pipework/vessels/control panel otherwise serious mechanical damage/destruction could 
occur causing injury to people or property. 
0.1.5
The equipment must not be heated/chilled beyond the maximum/minimum working temperature 
as stated on pumps/pipework/vessels/control panel otherwise serious mechanical 
damage/destruction could occur causing injury to people or property. 
0.1.6
Any damage to equipment, pumpset, vessels, pipework or system components caused by 
misapplication, mishandling or misuse could lead to Electric shock hazard, Burns hazard, Fire hazard, 
Flooding hazard or cause injury to people or property. 
0.1.7
This equipment may contain moving/rotating parts that must remain guarded. Removal of or 
missing guards could lead to serious personal injury. 
0.1.8
Pressure vessels must never be disassembled whilst in use, they contain high pressure air/gas 
charge which could cause injury to people or property.  
0.1.9
Ensure the base/foundation/plinth/wall to which the equipment is to be attached is sufficiently 
strong enough to carry the entire mass of the equipment including the water that it will contain 
under worst‐case fault conditions. E.g. fully saturated pressure vessel with no air charge, break tank 
full to overflowing, etc. Failure to observe this could cause serious mechanical damage/destruction 
resulting in injury to people or property. 
0.1.10
This equipment contains a fluid which may under certain circumstances leak/drip/spray fluid (e.g. 
servicing, repair or malfunction). Ensure any fluid discharge will not cause damage to the 
surroundings by taking appropriate action. E.g. install in a place that will not be damaged by leakage 
or install in a bunded area with adequate drainage. 
 
0.2  
CAUTIONS FOR INSTALLATION 
0.2.1
READ GENERAL SAFETY INFORMATION 0.0, WARNINGS 0.1 and CAUTIONS 0.2, 0.3 & 0.4 
0.2.2
The unit should only be installed/operated by a competent person; A competent person is someone 
who is technically competent and familiar with safety practices and the hazards involved. 
0.2.3
Do not lift the pumpset by pipework. Lift the pumpset by the container pallet using a pallet/forklift or 
crane by passing strops underneath the skid using a spreader bar. Failure to utilise these facilities will 
result in damage to the pumpset. 
0.2.4
Store in a dry place to avoid damp conditions deteriorating the equipment. 
0.2.5
Protect against dirt, damage and frost. It is absolutely essential that no foreign matter such as pipe 
thread swarf, welding slag, grit or stones are allowed to enter the set. Debris of this type can cause 
severe damage to the mechanical seals, diaphragms and impeller. Frost/freezing will damage 
pumps/pipework and control panel components. 
0.2.6
The equipment is only suitable for installation in a clean, dust free indoor environment, with adequate 
protection from heat and frost, and sufficient ventilation to ensure cooling of the motors. Ambient air 
temperature should be between 5 and 40 degrees centigrade, non‐condensating. Operation outside of 
these conditions could seriously damage the equipment. 
AquaTech-Pressmain Instruction Manual\AquaBreak
AquaBreak Series  