1.3.2  MONITORS AND DISPLAY PANELS  
Monitoring units are mounted on a wall suitable for connection to the sensors. (see note 1.3.3.6) 
Remote display units are wall mounted where required. 
1.3.3 ELECTRICAL 
1.3.3.1
READ GENERAL SAFETY INFORMATION 0.0, WARNINGS 0.1 and CAUTIONS 0.2, 0.3 & 0.4 
1.3.3.2
All wiring must comply with the latest edition of local wiring regulations. 
1.3.3.3
Wear anti‐static wrist strap at all times to avoid static discharge causing problems with the built in 
electronic program. 
1.3.3.4
For Tankmatic Panels that do not include pumps: Protection for the mains supply line to the unit ‐ 
Recommended circuit breaker 16Amp Type B or 10 Amp Type C. 
1.3.3.5
Connect incoming electrical mains supply to identified terminals in the monitoring unit (see Fig 3a or 
wiring diagram supplied). Ensure voltages and frequency indicated are correct and wiring diagrams 
correspond with supply mains data and that the supply fuse ratings are correct for the total current 
rating of the equipment provided.  
1.3.3.6
Connect Sensors to monitoring unit terminals, via a connection box when provided. (see Fig.3b or 
wiring diagram)  
1.3.3.7
For wiring between sensors, monitoring units, connection boxes, and remote display units use 
2
0.75mm
 minimum CSA with screen, e.g."CY" cable, earthed at panel end only. Screen earth should 
ideally be 360 degree termination to steel enclosure or alternatively to earth stud. Any unused cores 
must be earthed at panel end only. An alternative to screened cable is to use individual cores in 
EXCLUSIVE steel conduit.  
1.3.3.8
Where remote signals are required connect terminals in monitoring unit to remote display panel, 
heeding note 1.3.3.7 (see wiring diagram provided)  
1.3.3.9
Complete any required earth bonding. 
 
 
Aquatech‐Pressmain Instruction manual\Tankmatic smart relay MG‐LT 
 