8
U N I S E C D I G I TA L M A N U A L E D I F U N Z I O N A M E N TO E M A N U T E N Z I O N E
Consult the single-line diagram of the switchgear to
find the positions of the sensors that transmit
temperature values to the LHMI module.
• Ambient parameters: The temperature and
humidity values measured by the ambient sensor
are displayed in this screen.
Consult the single-line diagram of the switchgear to
find out where the ambient sensor is installed.
• Gas tank pressure screen: The pressure value of
the gas-insulated disconnector is displayed in this
screen.
• System setting screen: This screen displays the
firmware version of the monitor and the modbus
communication address.
NOTE
Consult manual 2NGA000492 for further
details about use of the LHMI module
2NGA000492
2.6 Alarms and corrective
Concentrator MDC4 -M is configured by ABB with
warning and alarm thresholds for the temperature
measurements of the main circuit and for gas
pressure measurement.
Using the mobile App, the LHMI module or the leds
on the concentrator, you can check whether the
values measured in real time exceed the alarm
thresholds.
NOTE
The threshold values are defined on the
basis of the characteristics of the
components installed and the tests performed to
ensure the apparatus functions correctly.
The threshold values set by the manufacturer cannot
be changed.
Once one of the thresholds is exceeded, the
concentrator displays an alarm signal via the "Alarm"
led on the front of the concentrator while the
parameter that has exceeded the threshold is
specified in the LHMI module.
The measurement that exceeds the threshold also
appears in red in the mobile APP.
The example below shows a screen on the mobile
APP where one of the parameters is in the alarm
state: