10.Setup
The actuator only requires the basic settings (adaptation to the operating range) in order to be operated
with the standard or custumer specific configuration. Use the Local Control Panel (LCP) for these set-
tings. Use the appropriate configuration software for more detailed parameter changes or diagnosis
functions.
10.1Set-up via local control panel (LCP)
10.1.1Operating elements
1. Write-protect switch
2. LED for 100% position
3. Drive buttons
4. Reset button
5. Power LED
6. RS 232 socket
7. Potential toggle switch
8. LED for 0% position
9. Accept button (0%)
10. Accept button (100%)
5
10
4
9
8
1
Figure 13: Local Control Panel (LCP)
The actuator range is not preset in factory!
10.1.2Setup procedure
- Undo the screws of the LCP cover
- Swing the cover to the side
10.1.3Initial situation
- Electronics connected to power supply and actuator
- Write-protect switch (1) set to "OFF" position
- Electronics in operating mode "MAN" (no signal on DI 1)
- No fault (if a fault occurs, both LEDs flash alternately at 4 Hz)
(Default setting: OFF)
Indication if adjustment procedure, saved position, or fault by different
flash frequencies.
Press to cause drive motion
Press to restart processor
Indicates available mains supply
Connection socket to PC
Connection of reference potential to the system or protective earth (by
default set to system) of electronic unit
Indication if adjustment procedure, saved position, or fault by different
flash frequencies..
Press to define current position as 0%; simultaneously press push but-
ton 9 + 10 to complete the adjustment procedure.
Press to define current position as 100%; simultaneously press push
button 9 + 10 to complete the adjustment procedure
2
3
7
6
(r0110rxa)