Siemens SIMATIC ET 200SP HA Manuale - Pagina 22

Sfoglia online o scarica il pdf Manuale per Apparecchiature industriali Siemens SIMATIC ET 200SP HA. Siemens SIMATIC ET 200SP HA 32. Distributed i/o devices busadapter for distributed i/o
Anche per Siemens SIMATIC ET 200SP HA: Manuale (50 pagine), Manuale (34 pagine), Manuale (38 pagine), Manuale dell'apparecchiatura (44 pagine), Manuale dell'apparecchiatura (50 pagine), Manuale dell'apparecchiatura (38 pagine), Manuale dell'apparecchiatura (46 pagine), Manuale dell'apparecchiatura (42 pagine), Manuale dell'apparecchiatura (44 pagine), Manuale dell'apparecchiatura (36 pagine), Manuale dell'apparecchiatura (38 pagine)

Siemens SIMATIC ET 200SP HA Manuale
Displays and interrupts
6.1 Status and error displays
LK1/LK2 LEDs on the BusAdapter
Table 6-6
Status and error displays of the LK1/LK2 LEDs
LED
LK1/LK2
There is no Ethernet connection between the PROFI‐
NET IO interface of your PROFINET device and a
Off
communication partner (e.g. IO controller).
There is an Ethernet connection between the PROFI‐
NET IO interface of your PROFINET device and a
On
communication partner (e.g. IO controller).
The "Node flash test" is run (the RN/ER/MTLEDs also
flash).
Flashes
Operating principle
The LED error display provides information on the cause of the error. After notification by the
flash signal, the error type is displayed followed by the error location/error code.
The LED error display
● takes precedence over all other states that are displayed by the ERROR and MAINT LEDs.
● remains switched on until the cause of the error is eliminated
Table 6-7
Display of error type and error location
Sequence
1
ER and MT LEDs flash 3x at 0.5 Hz
2
MT LED flashes at 1 Hz
3
ER and MT LEDs flash 3x at 2 Hz
4
ER LED flashes at 1 Hz
5
MT LED flashes at 1 Hz
6
Repeat steps 1 to 5 until the cause of the error has been eliminated.
Error display
Table 6-8
Error type
(MAINT)
1
22
Meaning
Description
Indication of the error type
Display of error type (decimal)
Indication of error location/error code
Display of tens digit (decimal) of the error location / error code
Display of ones digit (decimal) of the error location / error code
Error display
Cause of error
● No server module
● Interruptions on the backplane bus
● Short-circuit on backplane bus
Remedy
Check whether the bus cable to the switch/IO control‐
ler is interrupted.
---
---
Solution
Check the configuration of the
ET 200SP HA.
Interface Module IM 155-6 PN HA (6DL1155-6AU00-0PM0)
Manual, 05/2017, A5E39262148-AA