3.2
Configuration of the "Order Creation" dialog
The "Order Creation" dialog offers numerous possible settings to tailor the dialog to customer-
specific requirements. These settings are specified during the engineering phase directly at
the dialog control @FB_OrderCreation.pdl using WinCC Graphics Designer or through a user-
specific script.
Note
If configuration changes are required, it is recommended to make a copy of
@FB_OrderCreation.pdl.
Possible settings are described below:
Control Settings (object properties)
Name
FormulaCategoryMode
FormulaCategoryOperation
FormulaCategoryFilter
RecipeOperation
Advanced Process Functions SIMATIC BATCH Integration
Function Manual, 07/2016, A5E38719543-AA
Description
Options:
● enabled:
The operator must select a formula category before he/she can select the
relevant formula.
● disabled (default):
The operator can select the recipe or formula without previously selecting a
formula category.
Options:
● enabled (default):
The operator can select a formula category.
● disabled:
The operator is not authorized to select a formula category.
● Filter for selectable formula category names. Formula categories are
displayed when their name starts with FormulaCategoryFilter.
● No default
● Can be set in Graphics Designer or in script.
● If only one formula category matches the filter, this will be selected
automatically.
Options:
● enabled (default):
The operator can select a formula / recipe.
● disabled:
The operator is not authorized to select a formula / recipe.
Amendment on Engineering Manual
3.2 Configuration of the "Order Creation" dialog
13