Technical specifications

The technical specifications of the AddFEM SoE correspond to those of the AddFEM and are
described in the correspondingly named section in the "AddFEM (Front End Module)"
operating instructions. The document is available under the following link:
Internet (http://www.siemens.com/automation/service&support)
6.1

Technical specifications of AddFEM SoE

Number of SoE channels at the Add-
FEM SoE
Execution
Cycle time
Response time
Remaining resources
30
31 binary inputs
Digital inputs: Channel 1 ... 3 and 5 ... 16 (interface X6)
Digital outputs/inputs: Channel 17 ... 32 (interface X7)
The FEF SoE are executed on the co-processor of the
AddFEM SoE.
The execution takes place in parallel to the functions signal
acquisition and data exchange via PROFIBUS DP that are
executed by the main processor of the AddFEM SoE.
All 31 binary outputs are processed cyclically and in parallel
within the fixed set cycle time of 0.666 ms.
The following processing times have to be taken into con-
sideration for the cyclic processing time of the 31 digital
input channels:
For data exchange between the two processors
For the signal conditioning
The total period until the messages are available in the host
also depends on:
The set transport interval
The alarm processing time of the host (data transport
mechanism)
With the maximum configuration of 31 digital input channels,
at least the following resources remain that can be used
parallel to the FEF SoE for further functions:
Analog inputs (AI): 12
Analog outputs (AQ): 8
Digital inputs (DI): –
Digital outputs (DQ): –
Counters (FI): –