Article number
Update time for RT
Interface types
Protocols
RJ 45 (Ethernet)
Number of connections
Redundancy mode
Media redundancy
CPU 1515R-2 PN (6ES7515-2RN03-0AB0)
Equipment Manual, 11/2022, A5E42009914-AD
–
Updating times
for send cycle of 1 ms
–
2. Interface
•
RJ 45 (Ethernet)
Number of ports
•
•
integrated switch
IP protocol
•
•
PROFINET IO Controller
•
PROFINET IO Device
•
SIMATIC communication
•
Open IE communication
Web server
•
•
Media redundancy
Interface types
100 Mbps
•
•
Autonegotiation
Autocrossing
•
•
Industrial Ethernet status LED
Protocols
PROFIsafe
Number of connections, max.
•
•
Number of connections reserved for
ES/HMI/web
Number of S7 routing paths
•
•
PROFINET system redundancy (S2)
•
PROFINET system redundancy (R1)
–
MRP
–
MRP interconnection, supported
MRPD
–
Technical specifications
6ES7515-2RN03-0AB0
The minimum value of the update time also
depends on communication share set for
PROFINET IO, on the number of IO devices, and
on the quantity of configured user data
1 ms to 512 ms
Yes; X2
1
No
Yes; IPv4
No
No
Yes; Only Server
Yes
No
No
Yes
Yes
Yes
Yes
No
128
10
16
Yes
No
Yes; MRP Automanager according to IEC 62439-2
Edition 2.0
Yes; as MRP ring node according to IEC 62439-2
Edition 3.0
No
39