Siemens SIMATIC S7-200 Manuale del conducente - Pagina 7

Sfoglia online o scarica il pdf Manuale del conducente per Apparecchiature industriali Siemens SIMATIC S7-200. Siemens SIMATIC S7-200 28. Ethernet gateway for simatic mpi/ profibus driver
Anche per Siemens SIMATIC S7-200: Manuale (30 pagine), Manuale (35 pagine), Manuale (49 pagine), Manuale (18 pagine), Manuale del sistema (20 pagine)

Siemens SIMATIC S7-200 Manuale del conducente
7
Parity: Specify the type of parity for the data. Options include Odd, Even, or None.
Stop Bits: Specify the number of stop bits per data word. Options include 1 or 2.
Flow Control: Select how the RTS and DTR control lines are utilized. Flow control is required to communicate
with some serial devices. Options are:
None:  This option does not toggle or assert control lines.
l
DTR:  This option asserts the DTR line when the communications port is opened and remains on.
l
RTS:  This option specifies that the RTS line is high if bytes are available for transmission. After all
l
buffered bytes have been sent, the RTS line is low. This is normally used with RS232/RS485 converter
hardware.
RTS, DTR:  This option is a combination of DTR and RTS.
l
RTS Always:  This option asserts the RTS line when the communication port is opened and remains
l
on.
RTS Manual:  This option asserts the RTS line based on the timing properties entered for RTS Line
l
Control. It is only available when the driver supports manual RTS line control (or when the properties
are shared and at least one of the channels belongs to a driver that provides this support).
RTS Manual adds an RTS Line Control property with options as follows:
Raise: This property specifies the amount of time that the RTS line is raised prior to data
l
transmission. The valid range is 0 to 9999 milliseconds. The default is 10 milliseconds.
Drop: This property specifies the amount of time that the RTS line remains high after data
l
transmission. The valid range is 0 to 9999 milliseconds. The default is 10 milliseconds.
Poll Delay: This property specifies the amount of time that polling for communications is
l
delayed. The valid range is 0 to 9999. The default is 10 milliseconds.
Tip: When using two-wire RS-485, "echoes" may occur on the communication lines. Since this
communication does not support echo suppression, it is recommended that echoes be disabled or a RS-485
converter be used.
Operational Behavior
Report Comm. Errors:  Enable or disable reporting of low-level communications errors. When
l
enabled, low-level errors are posted to the Event Log as they occur. When disabled, these same
errors are not posted even though normal request failures are. The default is Enable.
Close Idle Connection:  Choose to close the connection when there are no longer any tags being
l
referenced by a client on the channel. The default is Enable.
Idle Time to Close:  Specify the amount of time that the server waits once all tags have been
l
removed before closing the COM port. The default is 15 seconds.
Ethernet Settings
Note: Not all serial drivers support Ethernet Encapsulation. If this group does not appear, the functionality
is not supported.
Ethernet Encapsulation provides communication with serial devices connected to terminal servers on the
Ethernet network. A terminal server is essentially a virtual serial port that converts TCP/IP messages on the
Ethernet network to serial data. Once the message has been converted, users can connect standard devices
that support serial communications to the terminal server. The terminal server's serial port must be
properly configured to match the requirements of the serial device to which it is attached. For more
information, refer to "How To... Use Ethernet Encapsulation" in the server help.
www. ptc.com
Siemens S7-200 Driver