Siemens SQS65.5 Manuale - Pagina 5

Sfoglia online o scarica il pdf Manuale per Controllore Siemens SQS65.5. Siemens SQS65.5 8. Sqs35 series, sqs65 series, sqs85 series, electric actuators for valves with a 5.5 mm stroke
Anche per Siemens SQS65.5: Istruzioni per il montaggio (2 pagine), Istruzioni per il montaggio (2 pagine)

Siemens SQS65.5 Manuale
SQS35... / SQS85...
SQS65...

Warranty

Maintenance

Technical data

Power supply
Operating data
Signal inputs
Signal outputs
Housing protection standard
Ambient conditions
Siemens Building Technologies
Landis & Staefa Division
Used in conjunction with valve types VVG44..., VVI52... or VXG44..., these actuators
generate a linear flow characteristic.
In conjunction with valve types VVG44..., VVI52... or VXG44... these actuators generate
an equal-percentage flow characteristic (factory-setting) via the integrated electronic
assembly. The flow characteristic can be changed to "linear" by repositioning the
connector.
The technical data (
p
,
max
applications described applies only to the Landis & Staefa valves listed in this data
sheet under "Compatibility".
The use of type SQS... actuators in conjunction with third-party valves invalidates
all claims under the Landis & Staefa warranty.
When servicing the valve: switch OFF the pump and power supply, close the main shut-
off valve in the pipework, release pressure in the pipes and allow them to cool down
completely. If necessary, disconnect electrical connections from terminals.
The actuator must be correctly fitted to the valve before re-commissioning.
Operating voltage
SQS35...
SQS65...
SQS85...
Power consumption
SQS35.00
SQS35.03
SQS35.50
SQS35.53
SQS65, SQS65.2
SQS65.5
SQS85.00
SQS85.03
Switching capacity of limit switchesTerminals 11 or 12
SQS35..., SQS85...
Type of control (control signal)
SQS85...
SQS65, SQS65.5
SQS65.2
Run-time
SQS35.00, SQS35.50, SQS85.00
SQS35.03, SQS35.53, SQS85.03
SQS65, SQS65.2, SQS65.5
Spring return feature
SQS35.50, SQS35.53, SQS65.5
Positioning force
Stroke
Terminal Y (SQS65, SQS65.5)
Terminal Y (SQS65.2)
Terminal R (SQS65, SQS65.5, SQS65.2)
Terminal U (SQS65, SQS65.5, SQS65.2)
Housing protection standard
Cable glands
Temperature of medium in the connected valve
p
, leakage rates, noise levels, service life etc.) given for the
s
AC 230 V ± 15 % , 50 / 60 Hz
AC 24 V ± 20 % , 50 / 60 Hz
AC 24 V ± 20 % , 50 / 60 Hz
2.5 VA
3.5 VA
5 VA
6 VA
4.5 VA
7 VA
2 VA
2 VA
AC 250 V, 6 A resistive / 2.5 A inductive
3-position
DC 0...10 V (proportional)
DC 2...10 V (proportional)
Opening or closing
150 s at 50 Hz
35 s at 50 Hz
35 s at 50 Hz
Closing time 8 s
400 N
5.5 mm
DC 0 ... 10 V, max. 0.1 mA
DC 2 ... 10 V, max. 0.1 mA
Resistance 0 ...1000 Ω
DC 0 ...10 V, max. 0.5 mA
IP54 to EN 60529
Pg11 (2 x)
+2 ... +130 °C
CM1N4573E / 06.2001
5/8