Siemens VBI60.25-16T Manuale - Pagina 4
Sfoglia online o scarica il pdf Manuale per Unità di controllo Siemens VBI60.25-16T. Siemens VBI60.25-16T 18. 2-port shutoff valves and 3-port changeover ball valves, pn 40, with internally threaded connection
Anche per Siemens VBI60.25-16T: Istruzioni per il montaggio (4 pagine), Istruzioni per il montaggio (4 pagine)
Cavitation
Cavitation increases wear and tear of the ball and seat and results in unwanted noise.
Cavitation can be prevented by not exceeding the differential pressures as per the flow
diagram and maintaining the static pressures depicted below.
Δp
max
p
1
P
3
M
J
Example with hot water:
Pressure p
Water temperature: 120 °C
The above diagram clearly indicates that the maximum permissible differential pressure is
Δp
max
Note on chilled water applications
To prevent cavitation in chilled water circuits, sufficient counter pressure must be supplied to
the ball valve outlet, e.g. using an additional butterfly valve downstream of the ball valve.
Maximum permissible differential pressure over the ball valve: See 80 °C curve in the above
diagram.
4
Siemens
Smart Infrastructure
= Differential pressure at a nearly closed ball valve
to largely avoid cavitation
= Static pressure at the ball valve inlet
= Static pressure at the ball valve outlet
Pump
Water temperature
at ball valve inlet: 500 kPa (5 bar)
1
→ 200 kPa (2 bar) at a nearly closed ball valve.
CE1N4213en
2020-02-20