Siemens SITRANS L Pointek ULS200 Manuale di istruzioni per l'uso - Pagina 29
Sfoglia online o scarica il pdf Manuale di istruzioni per l'uso per Interruttore Siemens SITRANS L Pointek ULS200. Siemens SITRANS L Pointek ULS200 47. Ultrasonic non-contacting switch
6.4
Low level alarm switch
This application uses the device to provide one or two low level alarms.
If the material can fall below the unit's range, the device loses the echo, and if prolonged,
defaults to fail-safe operation. The fail-safe default should be set to suit the application.
Fail-safe = 1, 2, or 3
①
Low-low (e.g. 4.5 m)
②
Low (e.g. 3.5 m)
③
Blanking (e.g. 0.5 m)
④
Range limit (e.g. 5.5 m)
Application adjustments
Alarm function
Alarm setpoint
Fail-safe alarm
Pointek ULS200
Operating Instructions, 01/2019, A5E32268616-AB
Fail-safe = 2 or 3
①
Low-low (e.g. 4.5 m)
②
Low (e.g. 3.5 m)
③
Blanking (e.g. 0.5 m)
④
Range limit (e.g. 5.5 m)
3 - low/low-low alarm
•
5 - low/LOE alarm
•
Set the low and/or low-low alarms to the desired
values.
1 - high
•
2 - low
•
3 - hold
•
29