GETTING STARTED

Helpful Hints
BBD43 (battery backup) provides a temporary power
source to DLE luminaires in the event that facility power is
lost or disconnected. One BBD43 unit will provide power to
a single light bar (see Note below) on a DLE luminaire for
90-180 minutes.
If you are installing BBD43 on a DLE-Uplight luminaire,
verify that the emergency light bar is oriented downward
(facing the floor) to ensure sufficient lighting in an
emergency situation. Refer to Identifying Emergency
Light Bar & BBD43 Placement to identify the emergency
light bar location, and the correct placement of the BBD43
unit, for each of the DLE luminaires.
Refer to Understanding DLE Luminaire Wiring
Configurations to identify slight variations within the
wiring compartments on each of the DLE luminaires.
Refer to Identifying Emergency Light Bar &
Note:
BBD43 Placement to identify the emergency light bar
location for each of the DLE luminaires. Note that the
DLE-48 luminaire requires two (2x) BBD43 units, one
installed on each end.
Identifying Emergency Light Bar
&
BBD43
Placement
Observe the location of the designated emergency light bar,
and the correct placement of the BBD43 unit(s), on each DLE
luminaire. If installing BBD43 on an uplight luminaire, ensure
the emergency lightbar is oriented downward (facing the
floor) to ensure sufficient lighting in case of an emergency
(Illustration 1).
Understanding DLE Luminaire
Wiring Configurations
Before you begin, observe the slight variations in the wiring
configurations among the DLE luminaires (Illustration 2).
Illustrations and wiring configurations in these
Note:
instructions reflect the DLE-24 luminaire
Prepare Luminaire and
Carefully, use a flat-head screwdriver to pry off the wiring
compartment cover on the DLE luminaire (Illustration 3).
Use a #2 Phillips
screwdriver to remove the bottom
®
faceplate screw. The screw is no longer needed
(Illustration 4).
Remove the BBD43 unit and accessories from the
packaging.
Note:
You must disconnect power to the luminaire before
installing a BBD43 unit. Failure to disconnect power will
result in hardware failure.
BBD43 Installation Instructions
BBD43
Hardware
INSTALLATION INSTRUCTIONS
Make Electrical Connections
Default wiring configurations enable facility power and data to
connect directly to the luminaire (see below). In this step, you
will extend these connections to include the BBD43 unit within
the circuit (Illustration 5). By default, the BBD43 unit ships
with the external power, data, and internal power (not shown)
cables disconnected.
Unplug the power connector (red/black or orange/gray)
from the DLE luminaire, and plug it into the two-position
header on the BBD43, as shown (Illustration 6).
Locate the power connection (red/black) coming from
the BBD43, and plug it into the two-position header on
the luminaire, replacing the connector you just removed
(Illustration 7).
Locate the data connector coming from the BBD43,
and plug it into the five-position header on the luminaire
(Illustration 8).
Refer to Understanding DLE Luminaire Wiring
Note:
Configurations for information on luminaire-specific
configurations.
Mount and Secure
BBD43
Secure the top retention hooks (2x) to the luminaire
faceplate, as shown (Illustration 9).
Rotate BBD43 to cover and align both open wiring
compartments. Ensure all wires are tucked safely into the
luminaire wiring compartment (Illustration 10).
Secure the bottom retention hook on the BBD43
unit to the bottom edge of the luminaire faceplate
(Illustration 11).
Use the screw (provided with BBD43) to secure the unit to
the luminaire.
BBD43 is built with three retention hooks (2x on top
Note:
of the unit housing, and one on the bottom) to secure the
hardware to the luminaire.
Connect Internal Power On
On the BBD43 unit, remove the access cover
(Illustration 12).
Connect the two-position battery connector within the
compartment (Illustration 13).
Replace the access cover.
To ensure maximum performance, BBD43 ships with
Note:
the battery disconnected. You must make this connection
before completing hardware installation.
to Luminaire
BBD43
Unit