Installation Guide
Important Notes for Return Air Temperature Sensor
SPLIT DUCTED UNITS (CAY/EVY or ELY)
Leave the factory fitted Return Air Temperature Sensor in place. If disconnected, a fault will be registered and
displayed in the screen. See the Split System Installation Guide, Air Temperature Setup for more details.
PACKAGE UNITS (PKY)
You must connect the factory supplied Return Air Temperature Sensor. If not connected, a fault will be registered and
displayed in the screen. Please refer to wiring diagram provided with your unit. See the Split System Installation Guide,
Air Temperature Setup for more details.
Follow the steps for assigning sensors, below, for the weighting of influence for both the return air temperature
sensor and the built-in CL01-2 sensor. Note that the Control Interface displays shown below are for Split Ducted Units,
these are for illustration purposes only. Displays for Package Units are without Use INDOOR sensor parameter.

05. Assigning Sensor

The CL01-2 Control Interface built-in sensor can be use to read your room temperature in combination with the return air
temperature sensor. This can be assigned via Service menu, as follows:
Service Menu
Display Progression:
Main Menu
F. Alarm History
G. Service
H. Manufacturer
G. Service
NOTE
Thermoregulation is under Service settings sub-level menu and password protected, enter the Service Password (7378) in
order to access this sub-menu.
From Thermoregulation 02 sub-level menu, you have the option to use 0% up to 100% CL01-2 sensor reading as follows:
Probe weight value
0 **
40
50
100
6
f. Service settings
c. Thermoregulation
G
Service menu
d. Working log
e. Communicate config.
f. Service settings
f. Service settings
CL01-2
Sensor Reading
0%
40%
50%
100%
Installation Guide - CL01-2 Control Interface Insert
Document: 9590-3026 Ver. 2 220907
CL01-2 Control Interface
Thermoregulation 02
Gf
Service menu
a. Working hour set
b. Probe adjustment
c. Thermoregulation
c. Thermoregulation
Room Air Temp
Example Display *
Sensor Reading
(CP05 / CP10)
Thermoregulation
Room Temperature
Use INDOOR sensor
100%
After Hours SW & Temp
Probe weight value
Room Temp.
Wall Cont Temp.
Control Value
Thermoregulation
Room Temperature
Use INDOOR sensor
60%
After Hours SW & Temp
Probe weight value
Room Temp.
Wall Cont Temp.
Control Value
Thermoregulation
Room Temperature
Use INDOOR sensor
50%
After Hours SW & Temp
Probe weight value
Room Temp.
Wall Cont Temp.
Control Value
Thermoregulation
Room Temperature
Use INDOOR sensor
0%
After Hours SW & Temp
Probe weight value
Room Temp.
Wall Cont Temp.
Control Value
Thermoregulation
Gfc2
Gfc
Room Temperature
Use INDOOR sensor
After Hours SW & Temp
Probe weight value
0
Room Temp.
18.0
o
c
Wall Cont Temp.
26.8
o
c
o
Control Value
18.0
c
Thermoregulation 02
Gfc2
** Default setting
0
o
18.0
c
26.8
o
c
o
18.0
c
Gfc2
40
18.0
o
c
26.8
o
c
18.0
o
c
Gfc2
50
18.0
o
c
26.8
o
c
18.0
o
c
Gfc2
100
18.0
o
c
26.8
o
c
18.0
o
c
* Legend:
Room Temp. = Return Air Temp Sensor Reading
Wall Cont Temp. = CL01-2 Built -In Sensor Reading