8: Set Right-Left swing; database type: [5.4] DPT_Percent_U8. set value:0- OFF; 1-
Angle1; 2- Angle2; 3- Angle3 ; 4- Angle4; 5- Angle5;6- Auto
9: Mode status read; data type: DPT_20.102 HVAC mode.
Read value: 0-OFF.1-Fan ; 2-Cool ; 3-Heat ; 4-Auto;5-Dry.
10: Indoor unit ambient temperature read; data type: DPT_9.001 temperature(°C).
11: Set temperature Non Auto Mode read; data type: DPT_9.001 temperature(°C) .
12: Set Heat temperature of Auto Mode read; data type: DPT_9.001 temperature(°C) .
13: Set Cool temperature of Auto Mode read; data type: DPT_9.001 temperature(°C) .
14: Fan speed read; data type: [5.4] DPT_Percent_U8
Read value: 1-speed1; 2-speed2; 3-speed3; 4-speed4; 5-speed5; 6-speed6;
7-speed7; 8-Auto
15: Fan Right-Left swing status read; database type: [5.4] DPT_Percent_U8.
Read value:0- OFF; 1- Angle1; 2- Angle2; 3- Angle3 ; 4- Angle4; 5- Angle5;6- Auto
16: Fan Right-Left swing status read; database type: [5.4] DPT_Percent_U8.
Read value:0- OFF; 1- Angle1; 2- Angle2; 3- Angle3 ; 4- Angle4; 5- Angle5;6- Auto
17: Auxiliary Heater status read; data type: DPT_1.001 Switch.
Read value: 0-Auxiliary Heater OFF,1-Auxiliary Heater ON
18: Alarm state read; data type: DPT_1.005 alarm
Read value: 0-no alarm; 1-alarm
19: ON/OFF status; data type: DPT_1.001 switch
Read value: 0-OFF, 1-ON
20: ON/OFF; data type: DPT_1.001 switch
Set value: 0-OFF; 1-ON
21: Set auto mode; data type: DPT_1.001 switch
Set value: 1-set as auto mode