15 - HOME AUTOMATION KIT

"INPUT CONTACT" WIRE ON/OFF (J13 - green)
The status of this input affects system operation according to the following:
Contact OPEN : system does not operate (always OFF) – inputs from wireless remote controller are not processed.
Contact CLOSED: system operates in the normal way according to the inputs coming from wireless remote controller.
"OUTPUT CONTACT" WIRE ALLARM (J3 - red)
This connector is directly tied to the contact (normally open) of a power relay which activates every every time the fol-
lowing alarm condition occur:
RAT damaged
ICT damaged
Communication error
Fault on outdoor unit
In this case when alarm happens, on poles 1 and 3 of J3 connector, 220-240 VAC-50Hz voltage is available.
Max electrical current: 1A

16 - JUMPER

JP1 - JP2
OPEN: Factory setting. Do not change. .
JP3
CLOSE: Factory setting. Do not change.
JP4
OPEN: Factory setting. Do not change.
JP5
OPEN: Termination resistor (200 Ω) communication bus not inserted. Factory setting.
CLOSE: Termination resistor (200 Ω) communication bus inserted.
JP6
OPEN: Termination resistor (200 Ω) communication bus 2 not inserted. Factory setting.
CLOSE: Termination resistor (200 Ω) communication bus 2 inserted.
ON / OFF
ALARM
15