Cisco APIC L4 Manuale di installazione e assistenza - Pagina 24

Sfoglia online o scarica il pdf Manuale di installazione e assistenza per Server Cisco APIC L4. Cisco APIC L4 46.

Cisco APIC L4 Manuale di installazione e assistenza
Installation Warnings and Guidelines
Warning
To prevent the system from overheating, do not operate it in an area that exceeds the maximum
recommended ambient temperature of: 35° C (95° F).
Statement 1047
Warning
The plug-socket combination must be accessible at all times, because it serves as the main
disconnecting device.
Statement 1019
Warning
Installation of the equipment must comply with local and national electrical codes.
Statement 1074
Warning
This unit is intended for installation in restricted access areas. A restricted access area can be
accessed only through the use of a special tool, lock, and key, or other means of security.
Statement 1017
Warning
This product relies on the building's installation for short-circuit (over current) protection. Ensure
that the protective devices is rated not greater than 20A (North America), 16A (Europe),and 13A
(UK).
Statement 1005
Caution
To ensure proper airflow it is necessary to rack the servers using rail kits. Physically placing the units
on top of one another or "stacking" without the use of the rail kits blocks the air vents on top of the
servers, which could result in overheating, higher fan speeds, and higher power consumption. We
recommend that you mount your servers on rail kits when you are installing them into the rack because
these rails provide the minimal spacing required between the servers. No additional spacing between
the servers is required when you mount the units using rail kits.
Caution
Avoid uninterruptible power supply (UPS) types that use ferroresonant technology. These UPS types
can become unstable with systems such as the Cisco UCS, which can have substantial current draw
fluctuations from fluctuating data traffic patterns.
Cisco APIC M4/L4 Server Installation and Service Guide
20
Installing the Server