Cisco C880 M4 Manuale di installazione dell'hardware - Pagina 6

Sfoglia online o scarica il pdf Manuale di installazione dell'hardware per Server Cisco C880 M4. Cisco C880 M4 23. System event log collection
Anche per Cisco C880 M4: Manuale di servizio supplementare (27 pagine), Manuale operativo (48 pagine), Manuale di avvio rapido (2 pagine), Manuale di aggiornamento del firmware (5 pagine)

Cisco C880 M4 Manuale di installazione dell'hardware
1.3

Installation Specifications

This section explains installation specification of each model.

1.3.1 Installation Specifications (Cisco C880 Server)

Dimensions
Width
[mm (in.)]
Depth (*1)
Length
Mass [kg (lb)] (*2)
Conditions for
Max. calorific
air conditioner
value
[kJ/h (BTU/h)]
Displacement
[m3/min (ft
(*3)
Temperature and
Humidity
conditions (*4)
Noise [dB] (*7, *8)
Acoustic power level [B] (*8)
Permissible
Vibration [m/s
(gal)]
Permissible dust level [mg/m
Power supply
Input voltage and source resultant pulse number
conditions
Frequency and fluctuating Range
Max power
consumption /
apparent power
Power factor (*10)
Inrush current [A] [Rush hours] (*11)
Leak current [mA] (*12)
*1: Dimensions without protrusions
*2: Numeric value when each optional device is mounted for maximum number of options.
However, rail for mounting rack (5.7kg) and cable type are not included.
Mass as per the installation configuration can be calculated using formula as shown below.
Device mass = 77 + (9.6 * A) + (2.5 * B) + (1.8 * C) + (3.3 * D) [kg]
A = Number of mounted SB (Minimum 1 to Maximum 4)
B= Number of mounted IOU (Minimum 1 to Maximum 4)
C= Number of mounted PSU (Minimum 2 to Maximum 6)
D= Number of mounted DU (Minimum 0 to Maximum 2)
TABLE 1.2 Installation Specifications (Cisco C880 Server)
Items
Interruptible power source
High efficiency power supply (*13)
Recommended environmental
3
/min)]
temperature
Max.
At the time
of operation
Downtime
(*6)
At the time of operation (Including
2
standby)
Downtime (*9)
At the time
of operation
Downtime
Temperature [°C (°F)]]
Humidity [%RH]
Max wet bulb
temperature [°C (°F)]]
Temperature [°C (°F)]]
Humidity [%RH]
Max wet bulb
temperature [°C (°F)]]
3
]
Interruptible power
source (*13)
High efficiency power
supply (*13)
3
Contents
445(17.52)
782(30.79)
438(17.25) 10U
143(315)
21,600(20,500)
20,900(19,800)
12(424)
28(989)
(*5)
20 to 80
29 (84.2)
0 to 50 (32 to 122)
8 to 80
29 (84.2)
60
7.8
4.0 (400) (Composite seismic
wave)
10.0 (1000) (Composite
seismic wave)
0.15
200 to 240 VAC±10 %
50/60 Hz + 2/-4%
6.00 kW/6.19 kVA
5.81 kW/5.99 kVA
0.084 kW
0.95 or more
20 or less
6.9 or less