finder 19.6K Manuale - Pagina 13
Sfoglia online o scarica il pdf Manuale per Controllore finder 19.6K. finder 19.6K 17. Knx actuator
1.9 List of general configuration parameters (valid for each Channel)
Parameter
PAR_Value Force ALL Out
Forcing status of all Channels with highest priority
PAR_Enable Keyboard
Enable local keyboard for manual activation of Channels on test phase
1.10 Detailed description of the parameters of Channel configuration page
1.10.1 Par_Contact Type
•
Property Datatype: PDT_UNSIGNED_8bit
•
Datapoint Type: none
•
Range: 0÷1
It defines the contact type, normally open (NO = default) with the value 0, normally closed (NC) with the value
1. If the parameter is set to NO, the OFF state will correspond to relay/circuit open. If the parameter is set to NC
value in the OFF state will correspond to relay/circuit closed.
1.10.2 PAR_Startup
•
Property Datatype: PDT_UNSIGNED_8bit
•
Datapoint Type: none
•
Range: [0÷2]
It defines the channels condition at startup. Value 0 always select Off (default), value 1 always select On, value
2 after downloading the application the device will save the status of the channels at each change in a non-
volatile memory location (EEPROM), in order to recover it correctly at power-on. If the device has never been
programmed via the ETS, the state set will be the default value stored in EEPROM.
1.10.3 PAR_Function
•
Property Datatype: PDT_UNSIGNED_8bit
•
Datapoint Type: none
•
Range: [0÷5]
It defines the function associated with the channel in accordance with Table 3:
Value
Meaning
0
Switch On/Off
(default)
1
On delayed
2
Off delayed
3
Blinking
5
Stairs Light
1.10.4 PAR_On Delay (s)
•
Property Datatype: PDT_UNSIGNED_16bit
•
Datapoint Type: None
•
Range: [1÷65535]
It defines the waiting time in seconds from the reception of the DPT_Channel X Set ON/OFF = On message
before switching a channel in the ON status. Default value is 5. The maximum value is a waiting of about 18
hours.
FINDER SpA
which is the last channel status before power off or device reset. selecting value
Ver. 2018
Related parameters
None
PAR_On Delay (s)
PAR_Off Delay (s)
PAR_Blink On (s), PAR_Blink Off (s)
PAR_Stairs Light Time (s)
Table 3