finder 19.6K Manuale - Pagina 7

Sfoglia online o scarica il pdf Manuale per Controllore finder 19.6K. finder 19.6K 17. Knx actuator

finder 19.6K Manuale
1.5.1.3
When the PAR_Function
ON/OFF = On message the channel starts to blink following PWM mode with the ON status
duration set by the PAR_Blink On (s) parameter and the OFF one by the PAR_Blink Off (s)
parameter. The values of these durations can be changed run-time via the DPT_Channel X-
Blink On Time (s) and DPT_Channel X- Blink Off Time (s) messages without overwriting
parameters values. The blinking cycle always begins with the full execution of the ON time
programmed. In the figure are not shown the DPT_Channel X - Status Inverted messages
that are sent as well from the device in correspondence with the status changing.
1.5.1.4
When the PAR_Function pa
Set ON/OFF = On message the channel status, if it was OFF, switches ON after a time set by
PAR_On Delay (s) parameter. The subsequent receipt of the message with the Off value
switches channel status from ON to OFF immediately. If the channel status is ON and the
device receives again the message DPT_Channel X
once delay has elapsed the DPT_Channel X - Status and DPT_Channel X - Status Inverted
messages will be sent on the bus. The delay time can be changed run-time via the
DPT_Channel X
are not shown the DPT_Channel X - Status Inverted messages that are sent as well from the
device in correspondence with the status changing. The functioning with the PAR_Function
DPT_Channel X Set ON/OFF = Off message, while the activation takes place immediately.
FINDER SpA
switching example
On d
switching example
On Delay (s) message without overwriting parameter value. In the figure
Ver. 2018
Blinking . By receiving the DPT_Channel X Set
Set ON/OFF = On, the cycle restarts and
is similar. In this case the delay starts by receiving the
KNX Actuator 19.6K
By receiving the DPT_Channel X
7