5.4 Timers setting
a) Auto close time set
Set DISP1 On, push and hold on PED for the auto close time setting. Now the red and green
LED flash fast alternatively, when reached the required time simply release PED button. Set
DIP1 OFF. The gate controller will back to working mode.
b) Lock pulse time set
Push and hold on OSC for the lock pulse time setting. Now the red and green LED flash fast
alternatively, and when gate reached the required time, simply release OSC button. Set DIP1
OFF. The gate controller will back to working mode.
5.5 SPE (special) time setting mode
To get into special setting mode, turn power off, set DIP1 on. Push and hold CLS button then turn
power on, LED will be on for short time, after LED off simply release CLS button. Gate controller is
getting into special time setting mode.
a) Reserved
Push and hold OPN reserved for late use.
b) Reserved
Push and hold PED reserved for late use.
c) PE trig close time
Push and hold on CLS for the PE trig close time setting. Now the red and green LED flash fast
alternatively and when gate reached required time, simply release CLS button.
d) Reserved
Push and hold OSC reserved for late use.

5.6 Factory default setting

Timer
F/Setting
Full Open Length
15M
PED Open Length
5M
Auto Close Time
30 sec.
Lock Pulse Time
0.8 sec.
Motor Stop Time
1.0 sec.
Sync Delay Time
Reserved
PE Auto close Time
2.0 sec
Reserved
Reserved
To restore factory setting, turn power off and set DIP1 on, push and hold CLS button then power
on. While hold CLS button, set DIP1 off, release the CLS button. Now controller restored factory
setting from memory.
Attention: First time power up, for different working mode will be different. If in Mode-1, the
motor will run at low speed in close direction (if DIP6 is on) and hit receiving post. Next open
command gate will open at low speed until to fully opened. The controller will calculate the gate
length and compare it with original gate length. If it is right, the gate will back to normal
operation, otherwise, gate will run at low speed. If in Mode-2,3,4
P750V5.0 industrial gate motor manual
Timer Setting
Step
Setting Method
0.7mm
STD& OPN Button
0.7mm
STD& OPN+PED Button
0.1sec.
STD& PED Button
0.1sec.
STD& OSC Button
0.1sec.
SPE& OPN Button
0.1sec.
SPE& PED Button
0.1sec
SPE& CLS Button
0
SPE& OSC Button
10
Range
No limitation
No limitation
0-6550sec.
0-25sec.
0-25sec.
0-25sec.
0-25sec
0