AEMT TIME MARK B2732 Manuale - Pagina 2

Sfoglia online o scarica il pdf Manuale per Strumenti di misura AEMT TIME MARK B2732. AEMT TIME MARK B2732 2. Single-phase current monitor

AEMT TIME MARK B2732 Manuale
MODEL 2732
R e a d A l l I n s t r u c t i o n s B e f o r e I n s t a l l i n g , O p e r a t i n g o r S e r v i c i n g T h i s D e v i c e .
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 2732.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
INSTALLATION
Connect the control wiring to the terminals with the contact
markings (refer to the diagram on the unit). Apply power.
For manual reset, a jumper connection is added on the reset
terminals and the reset button on the top of the monitor is
used.
For remote reset, a remote normally-closed button can be
added (both manual reset buttons can be used in this
configuration).
ADJUSTMENT
Set the time delay to the required amount of delay. If the
desired trip level is known, set the trip adjustment to that point.
A slight adjustment up or down may be necessary to allow for
tolerance variations.
Usually a trip is desired only if the current changes from the
present nominal.
For calibration, turn the TRIP DELAY
clockwise to the maximum delay.
Turn the TRIP LEVEL slowly up (or down) until the yellow
TRIP indicator comes on. Turn the adjustment back until the
L E D just goes out (if the manual reset is used, press and hold
the reset button during this step).
Reset the time delay to the previous setting.
TROUBLESHOOTING
Should the Model 2732 Single Phase Current Monitor fail to
operate, check all connections. Verify that power is present,
and check all fuses. Should problems persist, contact the
factory at 800-862-2875 for assistance.
WARRANTY
The Model 2732 Single Phase Current Monitor is warranted
to be free from defects in materials and workmanship for one
year.
Should this device fail to operate, we will repair or
replace it for one year from the date of purchase.
complete warranty details, see the Terms and Conditions of
Sales page in the front section of the Time Mark catalog.
Telephone: Main -
(918) 438-1220
Sales - (800) 862-2875
Fax:
(918) 437-7584
E-mail:
Internet:
http://www.time-mark.com
Single-Phase Current Monitor
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
Installation Instructions
TYPICAL APPLICATION
Under-Current with Alarm; Manual Reset
TYPICAL APPLICATION
Over-Current with Alarm; Remote Manual Reset
For
Shows No Power Applied
Shows No Power Applied
1 1 4 4 0 E a s t P i n e S t r e e t
T u l s a , O k l a h o m a 7 4 1 1 6
Doc No. 87A209 12/00
© 2000
TIME MARK CORPORATION
TIME MARK is a division of