2. 4. 4 Boost Time
only enabled with Room Thermostat on/off and
temperature adjustment activated (parameter 421 or
521 or 621 on 01 = Basic temperature adjustment)
This parameter can be used to set the delay time before
the automatic increase in fl ow temperature, in steps of
4°C (max. 12°C). If the value of this parameter remains at
00 the function is not activated.
2. 4. 5 Circulation pump MAX
speed
GENUS PREMIUM EVO HP 85/100/115/150
with optional pump kit - modulating
2. 4. 6 Circulation pump MIN
speed
GENUS PREMIUM EVO HP 85/100/115/150
with optional pump kit - modulating
2. 4. 7 Central Heating Pressure
detection device
ONLY FOR SERVICE - To be used only in substitution P.C.B.
2. 4. 9 External temperatura
correction
Only active with external sensor connected
DOMESTIC HOT WATER
2. 5
Activated with the boiler connected to a tank by an NTC sensor
2. 5. 0 COMFORT Function
This function keeps the external tank warm during the
periods in which the boiler is inactive.
When the function is enabled the text COMFORT appears
on the display.
Note: this function can be activated or deactivated by the
user as well - consult the User's Manual.
2. 5. 1 Comfort Anti-cycling Time from 0 to 120
2. 5. 2 Hot water fl ow delay
Anti "water hammering"
2. 5. 3 D.H.W. switch logic
2. 5. 4 Post-circulation and post-
ventilation after domestic
hot water is drawn
OFF = 3 minutes post-circulation and post-ventilation
after domestic hot water draw-off if the boiler temperature
measured requires it.
ON = always on for 3 minutes post-circulation and post-
ventilation after domestic hot water draw-off .
2. 5. 5 Delay start in Central
Heating after D.H.W.
request
34
value
from 0 to 60
16
(minutes)
from 75 to 100
100
from 40 to 100
0 = Temperature
2
Probes only
1 = Pressure switch
2 = Pressure sensor
from -3 to +3
0
0 = Disabled
0
1 = Time Based
(30 minute)
2 = Always active
0
minutes
from 5 to 200
5
(0.5 to 20 seconds)
0 = Anti-scale
0
(stop at > 67°C)
1 = At 4°C over set-
point
0 = OFF
1
1 = ON
from 0 to 30
0
(minutes)
description
notes
2. 5. 7 Anti-legionella Function
Activated with the boiler connected to a tank by an NTC
sensor
This function prevents the formation of Legionnaire's
disease bacteria which may develop in the piping
and indirect cylinders at temperatures between 20°C
and 40°C. If activated, whenever the indirect cylinder
temperature stays below 59°C for over 100 hours, the
boiler heats the water in the indirect cylinder until it
reaches 65°C for 30 minutes.
2. 5. 8 Antilegionella frequency
2. 5. 9 Temperatura
obbiettivo
antilegionella
2. 6 BOILER MANUAL SETTINGS
2. 6. 0 Manual mode activation
2. 6. 1 Boiler pump control
2. 6. 2
Fan control
2. 6. 3 Diverter valve control
2. 7 TEST & UTILITIES
2. 7. 0 Test mode
Turn the encoder to select ON and press OK.
The boiler is forced to the maximum heating power.
Turning the encoder allows for selecting the D.H.W.
maximum or minimum power operating mode
It is possible to activate the Cleaning Function (Chimney
active) by pressing the Reset button for 10 seconds.
2. 7. 1 Air purge Function
Turn the encoder to select ON and press OK.
The Deaeration Cycle can be activated by pressing the
ESC button for 5 seconds.
2. 8 RESET MENU' 2
2. 8. 0 Reset factory settings
To reset all default parameter settings, press the OK button
4 ZONE 1 PARAMETER
4. 0 ZONE 1 TEMPERATURE SETTING
4. 0. 2 Fix temperature central
heating
To set only with Fixed Flow Temperaure of
Thermoregulation (see 421)
4. 2 ZONE 1 SETTING
4. 2. 0 Zone 1 Temperature range 0 = from 20 to 45°C
value
0 = OFF
0
1 = ON
from 24 to 720
100
(hours)
from 60 to 70 (°C)
66
0 = OFF
0
1 = ON
0 = OFF
0
1 = ON
0 = OFF
0
1 = ON
0 = OFF
0
1 = ON
0 = OFF
0
1 = ON
0 = OFF
1 = ON
Reset OK = yes
ESC = no
from 35 to 85 (°C)
70
(high temperature)
from 20 to 45 (°C)
25
(low temperature)
(low temperature)
1 = from 35 to 85°C
(high temperature)