Ariston GENUS PREMIUM EVO HP 150 Istruzioni per la progettazione, l'installazione e la manutenzione - Pagina 29

Sfoglia online o scarica il pdf Istruzioni per la progettazione, l'installazione e la manutenzione per Caldaia Ariston GENUS PREMIUM EVO HP 150. Ariston GENUS PREMIUM EVO HP 150 44. Wall-hung condensing gas boiler hp
Anche per Ariston GENUS PREMIUM EVO HP 150: Manuale d'uso (17 pagine), Manuale d'uso (24 pagine)

Ariston GENUS PREMIUM EVO HP 150 Istruzioni per la progettazione, l'installazione e la manutenzione
The boiler is protected from malfunctions by means of internal
checks performed by the electronic P.C.B., which stops the boiler
from operating if necessary. In the event of the boiler being shut off
in this manner, a code appears on the control panel display which
refers to the type of shut-off and the reason behind it.
Two types of shut-off may occur:

Safety shut-off

This type of error is "volatile", which means that the boiler starts up
again automatically as soon as the problem which caused the shut-
off is removed.
The display will visualise the error code and description.
"Fault 110 - Send Probe Damaged"
In fact, soon as the cause of the shut-off disappears, the boiler
starts up again and continues to operate normally.
If the boiler still indicates a safety shut-off , switch it off . Make sure
the external electric switch is in the OFF position, shut off the gas
valve and contact a qualifi ed technician.
ALERT
Call the technical service
Safety shut-off due to insuffi cient water pressure
If the water pressure inside the heating circuit is insuffi cient, the
boiler will perform a safety shut-off .
The error code "Fault 108 - Filling Needed" appears on the display
The system may be restarted, re-balancing the value, by using the
fi lling valve.
ALERT
Check the pressure on the pressure gauge and close the valve as
soon as it reaches 1 - 1.5 bar.
If the re-balancing request is performed on a frequent basis, switch
the boiler off , bring the external electric switch to the OFF position,
shut off the gas valve and contact a qualifi ed technician to check
for any leaks of water.
Operation shutdown
This type of error is "non-volatile", which means that it is not
removed automatically.
The display will visualise the error code and description.
"Fault 501 - No fl ame detected - Press the Reset button"
In this case the boiler does not restart automatically, but it may be
reset by pressing the
Fault 501
ALERT
No flame detected
Press the Reset button
Reset in progress
Fault 110
Send Probe Damaged
Fault 108
Filling Needed
button.
Fault solved
Important
If this shutdown occurs frequently, contact an authorised Technical Service
Centre for assistance. For safety reasons, the boiler will permit a maximum of 5
resets in 15 minutes (5 presses of the RESET button); at the 6th attempt within
this 15-minute period the boiler will shut down and may only be operated
again after the electricity supply has been disconnected. If the shutdown is
occasional or an isolated event, this is not a problem.
The fi rst fi gure of the error code (e.g. Errore 101) indicates within
which operational assembly the error occurred.
1 - Primary Circuit
2 - Domestic Hot Water Circuit
3 - Internal Electronic Part
4 - External Electronic Part
5 - Ignition and Detection
6 - Air inlet - fl ue gas outlet
7 - Multizone
Malfunction warning
This warning is shown by the display in the following format:
Warning 5P1 = 1st Ignit Failed
Warning 5P1
the fi rst fi gure indicating the operational assembly is followed by a P
(warning) and the code relating to the specifi c warning.
Table summarising error codes
Central Heating circuit
Display Description
101
Overheat
102
Pressure Sens Error
103
104
105
Insuffi cient circulation
106
107
108
Insuffi cient water (request fi lling)
110
C.H. Flow temp. probe circuit open / short circuit
112
C.H. Return temp. probe circuit open / short circuit
114
External sensor circuit open / short circuit
116
Floor Thermostat contact open
118
Heating delevery probe problem
1P1
1P2
Insuffi cient circulation indication
1P3
1P4
Insuffi cient water (request fi lling)
D.H.W. circuit
203
Tank Probe Damaged
205
DHW In Probe Open Circuit
209
Tank Overheat
Internal P.C.B.'s
301
EEPROM error
302
Comunication error
303
Main P.C.B. error
304
Too many (> 5) resets in 15 minutes
305
Main P.C.B. error
306
Main P.C.B. error
307
Main P.C.B. error
3P9
Sched.Maintanace-Call Service

boiler protection devices

29