Ariston micro SYSTEM 15 RFFI Manuale di istruzioni per l'installazione - Pagina 8

Sfoglia online o scarica il pdf Manuale di istruzioni per l'installazione per Caldaia Ariston micro SYSTEM 15 RFFI. Ariston micro SYSTEM 15 RFFI 44. Type c boilers
Anche per Ariston micro SYSTEM 15 RFFI: Manuale d'uso (16 pagine)

Ariston micro SYSTEM 15 RFFI Manuale di istruzioni per l'installazione
2.9
F
C
LUE
ONNECTIONS
BC
F
D
J
HI
F
. 2.5
IG
Ø 60/100 mm
F
. 2.6
IG
F
LUE
The provision for satisfactory flue termination must be made in accordance with BS
5440-1.
The appliance must be installed so that the flue terminal is exposed to outside air.
The terminal must not discharge into another room or space such as an outhouse or
lean-to.
It is important that the position of the terminal allows a free passage of air across it at
all times.
The terminal should be located with due regard for the damage or discolouration that
might occur on buildings in the vicinity.
In cold or humid weather water vapour may condense on leaving the flue terminal.
The effect of such "pluming" must be considered.
If the terminal is less than 2 metres above a balcony, above ground or above a flat
roof to which people have access, then a suitable terminal guard must be fitted.
When ordering a terminal guard, quote the appliance model number.
A suitable terminal guard is available from:
TOWER FLUE COMPONENTS
Morley Road
Tonbridge
Kent TN9 1RA
The minimum acceptable spacing from the terminal to obstructions and ventilation
openings are specified in F
F
G
A
E
K
L
G
The boiler is designed to be connected to a coaxial flue discharge system.
S
YSTEM
. 2.5.
IG
T
P
ERMINAL
OSITION
A - Directly below an openable window or other opening
B - Below gutters, soil pipes or drain pipes
C - Below eaves
D - Below balconies or car-port roof
E - From vertical drain pipes and soil pipes
F - From internal or external corners
G - Above ground or balcony level
H - From a surface facing a terminal
I - From a terminal facing a terminal
J - From an opening in the car port
(e.g. door, window) into dwelling
K - Vertically from a terminal in the same wall
L - Horizontally from a terminal in the same wall
8
mm
300
75
200
200
75
300
300
600
1200
1200
1500
300