1
Introduction
The FPC-1 is a self-contained aerosol activation module.
The FPC-1 includes a heat sensor that operates as a fixed-temperature or Rate-of-Rise
and fixed-temperature detector, input for optional manual activation switch and/or linear
heat detector, control circuitry, and activation of two FirePro Aerosol units.
The unit reports via open collector alarm condition, trouble condition, and provides
"watch-dog" pulses to indicate the unit is alive.
The module is operated by its own supervised power source.
The FPC-1 is not intended to replace fire detection and automatic extinguishing systems
that are required according to relevant regulations.
An open or disconnected aerosol generator will not interfere with the operation of the
other aerosol.
Figure 1
2
Installation
Only authorised people should install the FPC-1. Install the unit on the top surface of the
protected space or near the top as high as possible. Install the aerosol container
according to the manufacturer's specification.
Warning
Disconnect all power sources when installing the FPC-1 in protected spaces that
have power sources.
1.
Remove the module's top cover.
2.
Secure the module to the top surface of the protected space (see Figure 2 on page
2 for location of the openings for mounting screws).
3.
Connect the first aerosol extinguisher to the terminal marked "Match 1". Connect
the second aerosol extinguisher, if required, to the terminal marked "Match 2". Short
"Match 2" output if a second aerosol is not used.