Fireray 5000 Manuale d'uso - Pagina 10

Sfoglia online o scarica il pdf Manuale d'uso per Allarme fumo Fireray 5000. Fireray 5000 17. Motorised infrared optical beam smoke detector

Fireray 5000 Manuale d'uso
12. 'Set' 0/100 (Calibrate)
• When 'Set' is displayed press
• When 'S-00' is displayed, cover the Reflector with a non- reflective material and leave
covered, then press
• When 'S-01' is displayed, uncover the Reflector and leave uncovered, then press
• Repeat Steps 8 to 12 for any other Detectors found during the 'Find' process

13. System is Aligned

• Green LED on Detector will flash every 10 seconds, and Signal Strength should be between
99% and 101%
• Default values: 35% Fire Threshold, 10 second delay to Fire and Fault, Non-Latching mode
whilst the Reflector is still uncovered
10