Service & Maintenance
The Firetrace® systems can operate in a harsh environment and are occasionally subjected to
high temperatures and extreme vibration. It is essential that the systems are regularly serviced
to ensure their correct operation.
In order to comply with British Standard BS 5306 (section three) the following maintenance
tasks shall be carried out periodically.
The British standard recommends that each system is visually inspected every 3 months and
then fully serviced at maximum intervals of 12 Months by a competent engineer.
All FE-36 systems require discharge testing at maximum 10 Year intervals.
Firetrace® Limited recommends a visual inspection of a Firetrace® system at
The following checks shall be carried out on this inspection.
• Check the pressure gauge is reading mid-green.
• Carry out a visual check of the trace detection tube.
• Check all detection tube fittings for soundness.
• Check external surface of the cylinder for evidence of rust or corrosion.
• Report any potential problems immediately.
least every three months.