CALEFFI SATK30 Series Istruzioni per l'installazione, la messa in servizio e la manutenzione - Pagina 3
Sfoglia online o scarica il pdf Istruzioni per l'installazione, la messa in servizio e la manutenzione per Apparecchiature di registrazione CALEFFI SATK30 Series. CALEFFI SATK30 Series 16. Wall-mounted compact indirect heat interface unit
Dimensions
SATK30103HE
550
10
292,5
2
1
ON
DHW
CH
FAULT
159
65
101
530
A
3/4" M
Technical specifications S TK30103HE
Medium:
Maximum percentage of glycol:
Maximum medium temperature:
Max. working pressure: - primary circuit:
- secondary circuit:
- domestic water circuit:
Nominal DHW exchanger capacity:
Nominal heating exchanger capacity:
Maximum recommended primary circuit flow rate:
Maximum differential pressure on
domestic water modulating valves:
Domestic water circuit max. flow rate:
Minimum flow to activate domestic water flow meter: 2,7 l/min ±0,3
Electric supply:
Max power consumption:
Protection class:
Pump:
Pump by-pass setting:
Actuators:
Probes:
Safety relief valve setting:
Safety thermostat:
Expansion vessel:
- capacity:
- pre-charge value:
Pressure switch:
- opening:
- closing:
Materials
Components:
Fitting pipes:
Frame:
Protective shell cover:
Heat exchanger:
SATK30105HE
65
65
1,6 MPa (16 bar)
0,3 MPa (3 bar)
1 MPa (10 bar)
1,2 m
Dp 90 kPa (0,9 bar)
18 l/min (0,3 l/s)
230 V (ac) ±10% 50 Hz
UPM3 15-70
45 kPa (0,45 bar)
stepper 24 V
NTC 10 k
0,3 MPa (3 bar)
55°C ±3
0,1 MPa (1 bar)
40 kPa (0,4 bar)
80 kPa (0,8 bar)
brass EN 12165 CW617N
RAL 9010 painted steel
brazed stainless steel
550
10
298,5
65
2
1
ON
DHW
CH
FAULT
2
3
1
0
4
bar
59
65
207
65
530
B
1/2" M
Technical specifications S TK30105HE
Medium:
water
Maximum percentage of glycol:
30%
Maximum medium temperature:
85°C
Max. working pressure: - primary circuit:
Nominal DHW exchanger capacity:
40 kW
Nominal heating exchanger capacity:
15 kW
Maximum recommended primary circuit flow rate:
/h
3
Maximum differential pressure on
domestic water modulating valves:
Domestic water circuit max. flow rate:
Minimum flow to activate domestic water flow meter: 2,7 l/min ±0,3
Electric supply:
Max power consumption:
80 W
Protection class:
IP 40
Pump:
Pump by-pass setting:
Actuators:
Probes:
Safety relief valve setting:
Safety thermostat:
Expansion vessel:
7 l
Pressure switch:
Materials
Components:
Fitting pipes:
steel
Frame:
Protective shell cover:
EPP
Heat exchanger:
3
265
C
3/4" F
1,6 MPa (16 bar)
- secondary circuit:
0,3 MPa (3 bar)
- domestic water circuit:
1 MPa (10 bar)
Dp 165 kPa (1,65 bar)
27 l/min (0,45 l/s)
230 V (ac) ±10% 50 Hz
45 kPa (0,45 bar)
stepper 24 V
0,3 MPa (3 bar)
- capacity:
- pre-charge value:
0,1 MPa (1 bar)
- opening:
40 kPa (0,4 bar)
- closing:
80 kPa (0,8 bar)
brass EN 12165 CW617N
RAL 9010 painted steel
brazed stainless steel
water
30%
85°C
65 kW
15 kW
1,2 m
/h
3
80 W
IP 40
UPM3 15-70
NTC 10 k
55°C ±3
7 l
steel
EPP