Caleffi solar 252219HP Istruzioni per l'installazione, la messa in funzione e la manutenzione - Pagina 4

Sfoglia online o scarica il pdf Istruzioni per l'installazione, la messa in funzione e la manutenzione per Unità di controllo Caleffi solar 252219HP. Caleffi solar 252219HP 12. Tempering valve for solar and instantaneous applications

Flow rate graph
∆p (kPa)
150
140
120
100
90
80
70
60
50
45
40
35
30
20
20
18
16
14
12
10
9
8
7
6
5
4,5
4
3,5
3
2,5
2
1,8
1,6
1,4
1,2
1
Code
Ø (mm)
252212HP
15
252219HP
20
Use and flow rate
Caleffi series 2522HP tempering valves are typically installed at the hot water heater. In order
to maintain the set temperature, the tempering valve must have a minimum flow rate of 4 l/min.
When used in instantaneous hot water systems, the most stable conditions are achieved with
the hot water temperature set lower than 65°C and with a flow rate greater than 6 l/min.
The system should be sized in accordance with the current legislation in regard to the nominal
flow rate of each outlet.
The reference is AS/NZS 3500.1 Table 3.1.
Flow rate - Litres per minute
Kv (m
3
/h)
1,5
1,7
4
Ø 15 mm
Ø 20 mm
G (l/min)