Sfoglia online o scarica il pdf Manuale di istruzioni per l'installazione e la manutenzione per Camino da interno Economite RE32. Economite RE32 8. Gas conversion burner
V ELECTRICAL
Installation wiring and grounding of the burner must conform to
local codes, or, in their absence in the United States to
National Electric Code, ANSI/NFPA No. 70-1 latest edition; in
Canada, to Canadian Electrical Code Part 1, CSA Standard
C22.1.
Use 14 gage copper wire for line voltage wiring. Be sure to
hook up to permanently live circuit. Provide a fused on-off dis-
connect switch carrying a minimum 3 amp fuse.
The frame of the burner should be well grounded. A terminal
is provided on the strip for positive grounding.
Confirm that the polarity is correct -- hot wire to strip terminal
1, neutral 2 -- and that the neutral line is not subject to induced
low voltage (check 2 to earth ground) from other equipment, as
that can cause the flame safeguard to malfunction.
Each installation must include suitable limit control(s).
Existing oil burner combination operating and limit controls are
normally NOT SUITABLE for gas burner use.
Set the thermostat heat anticipator for the total current draw
handled by the thermostat. The current draw of the Economite
24V operating circuit is 0.9 amps.
CAUTION: Label all wires prior to disconnection when
servicing controls.
Wiring errors can cause improper
and dangerous operation. Verify proper operation after
.
servicing
COMBINATION
VALVE
MOTOR WITH INTERNAL
INTERLOCK SWITCH
SPLICE
BR
BK
PV
Y
R(Y)
MV/PV
BL
MV
TRANSFORMER
Y
W(BK)
BK
BL(Y)
T
T
GND
TERMINAL
STRIP
THERMOSTAT OR 24V OPERATING
CONTROL. IF NOT USED, JUMPER T-T
MOTOR
2
BK(W)
W(BK)
GROUND
BAR
MOTOR RELAY
SPST N.O.
Y
SPLICE
Y
GND
MV
BL
MV/PV
PV
WIRING AND
COMPONENTS:
TERMINALS:
FIGURE 6 Wiring Diagram
CAUTION: Do not add any power consuming devices in
the low voltage circuit as it could overload the transformer.
Do not use Motor Relay to operate any external devices as
the extra load could damage the relay contacts.
NOTE: If any of the original wiring as supplied with the
conversion burner must be replaced, it must be replaced with
type TFF wire or its equivalent.
CONNECTION DIAGRAM
S8600 ELECTRONIC CONTROL
BL
MV
Y
MV PV
BR
PV
W(BK)
GND
(NOT USED)
R(Y)
BURNER
Y
24V
MOTOR RELAY
GND
24V
2
BK
1
Y
4
3
SENSE
BL
SPARK
SPARK ELECTRODE
BK
SENSOR ROD
1
2
FUSED DISCONNECT
NEUTRAL
120/1/60
HOT
SERIES CONNECT ALL 120V OPERATING
AND/OR LIMIT CONTROLS
SCHEMATIC
NEUTRAL
120 V CONTROLS
M I
120/1/60
4
2
1
BK
BK
HOT
BK
THERMOSTAT OR 24V CONTROL
IF NOT USED, JUMPER T-T
Y
BL(Y)
24V
T(LEFT)
T(RIGHT)
1
3
BL
M
INTERLOCK SWITCH
R(Y)
R(Y)
24V
24V
GND
BL
MV
BK
SENSE
Y
MV/PV
SENSE ROD
SPARK
BR
PV
SPARK ROD
LEGEND
BY MIDCO
BY INSTALLER
TERMINAL STRIP
COMPONENT
ELECTRONIC CONTROL
SPLICE
VI PIPING
CAUTION: The available gas pressure should be within
the
limits
shown
in
Excessive pressure will damage Combination Valve and
Regulator. If the supply pressure exceeds the 14.0" W.C.
maximum, a suitable intermediate main regulator rated for
main and pilot loads must be installed ahead of the Main
Manual Shut-Off Valve shown in Figure 7.
The burner gas supply piping should branch off from the
main line as close to the gas meter as possible. Do not connect
to the bottom of a horizontal section. Use new black pipe and
malleable fittings free of cutting and threading burrs or defects.
Provide a sediment trap, union and 1/8" pressure tap in
piping close to burner as shown in Figure 7.
Use pipe joint compound approved for use with Liquid
Petroleum Gases.
Piping must comply with local codes.
To obtain the maximum firing rate of 300 MBH, the gas
supply piping must be sized to provide a minimum of 4.0" W.C.
pressure to the inlet of the combination valve when the burner
and all other gas utilization equipment are on. For a firing rate
of 225 MBH or less, 3.5" W.C. inlet pressure is sufficient.
When selecting the burner supply pipe size per Table 2, the
permissible pressure drop must be based on the pressure
available at the inlet to the supply pipe branch line when all
other gas utilization equipment is on.
NOTE: If there is more than 1.0" W.C. differential in the inlet
pressure to the burner compared to when all other gas
utilization equipment is off, refer to Section IX, last paragraph.
CAUTION: Because it is difficult to accurately control
pressure during supply pipe leak test, it is recommended
that the Combination Valve be disconnected. Exposing the
Combination Valve to a pressure over 1/2 (14" W.C.) PSIG
will damage the valve and void all warranties.
DANGER: Explosion hazard. Do not use oxygen for
pressure testing. An explosion could occur during initial
start-up.
If the burner piping must be rearranged because of space
limitations, be sure to carry out the general arrangement shown
in Figure 7. Install the combination valve in any position except
up-side down.
When the burner is installed in the vestibule of jacketed
equipment, it is recommended that the combination valve be
left adjacent to the burner within the vestibule. Install the Main
Manual Shut-Off Valve in the piping outside the jacket of the
equipment.
TYPE OF
PIPE
GAS
SIZE
NATURAL
1
Ú
2
PROPANE
NATURAL
3
Ú
4
PROPANE
NATURAL
1
PROPANE
NATURAL
1
1
Ú
4
PROPANE
TABLE 2: Supply Pipe Capacities in MBH
Capacities shown are for a total pressure drop of 0.3" W.C. For
higher permissible pressure drops, consult your fuel supplier.
Source: Gas Engineers Handbook-1974
-4-
the
SPECIFICATIONS
section.
APPROX. CAPACITY-MBH
LENGTH OF PIPE
10
20
40
100
60
90
60
50
130
145
100
200
80
275
190
130
105
300
300
200
165
125
245
195
150
300
300
300
300
235
300
300
300
300
60
80