6 APPENDIX

6.1 General Data

Ordering information
Product designation
Device designation
Type
Order number: Basic equipment
Mechanical data
Weight
Protection class
Dimensions (LxWxH)
Climatic stability
Temperature range for operation
Temperature range for storage
Vibration
Shock
Seismic
Electrical data
Power supply U
:
pwr
Excitation output current Ie:
Excitation output voltage
Test voltage:
Power supply U
against case, relay contact and CAN Bus
pwr
Relay contact against case
Relevant standards, CE conformity
EMC directive:
Generic emission standard *)
Product standard emission
Generic immunity standard
*) The emission limit values are kept only if the supply circuits Upwr is fed through a filter and the
power circuits are fitted with shielded cables.
User' Manual
Automatic voltage regulator UNITROL 1000-15
- DC
- Single phase
- Three phase
- Maximum continuous current until 55 ° C
- Overload for maximum 10 s
ABB Switzerland Ltd
16 to 300 V DC,
30 to 250 V AC, 40 to 600 Hz
9 to 250 V AC,
Document number
3BHS200200 E80
UNITROL
1000-PM40
Power Module 40 A
UNS 2114A-Z
3BHE015411 R0001
6.7 kg
IP20
220x285x154 mm
0 to +55 ° C
-20 to +75 ° C
IEC 60255-21-1, class 2
IEC 60255-21-2, class 2
IEC 60255-21-3, class 2
DC
0 to 600 Hz
40 A
80 A
0 to 350 V DC
3 kV DC, 2 s
2 kV AC, 1 min.
89/336/EEC
IEC 61000-6-4
IEC 61800-3, Annex D
IEC/EN 61000-6-2
3BHS201795 E80
Lang.
Rev. ind.
en
A
Page
18