Aerco AM 750W Manuale di applicazione - Pagina 6
Sfoglia online o scarica il pdf Manuale di applicazione per Scaldabagno Aerco AM 750W. Aerco AM 750W 20. Gas-fired boilers and water heaters venting application
Anche per Aerco AM 750W: Manuale di applicazione (8 pagine)
GF-146-V
TAG-0075_0B
1.3.4. OPTION 4: PVC/CPVC (Use Schedule 40 or thicker, Single-Wall,
Uninsulated Pipes)
When using Non-Metallic (Plastic) vent systems for Canadian installations, per CSA B149.1, use vent
systems that are certified to the Standard for Type BH Gas Venting Systems, ULC-S636. The plastic
components, primers and glues of the certified vent system must be from a single system
manufacturer and not inter-mixed with other manufacturers vent system parts.
1. PVC
•
ASTM F891
•
ASTM D2665
•
ASTM D1785
•
ASTM D2241
2. CPVC
•
ASTM D2846
•
ASTM F441
•
ASTM F442
1.4. FACTORY SUPPLIED INLET AND VENT CONNECTION COMPONENTS
All units are supplied with the appropriately sized PVC starter piece for venting. For starter pieces
intended for polypropylene or AL29-4C venting, contact the vent manufacturer directly.
Page 6 of 20
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
AM Series Venting
Application Guide
AM1 04/08/2014