Armstrong GP-2000 Manuale di installazione, funzionamento e manutenzione
Sfoglia online o scarica il pdf Manuale di installazione, funzionamento e manutenzione per Unità di controllo Armstrong GP-2000. Armstrong GP-2000 8. Pressure reducing valves
Anche per Armstrong GP-2000: Manuale (8 pagine), Manuale (2 pagine)
Typical Single Stage Reduction Installation (For Steam)
Integral Mount
Globe
Valve
Armstrong
Strainer
Minimum of 10 Inlet
Pipe Diameters from
PRV to First Turn
Armstrong
TVS-Trap
This bulletin should be used by experienced personnel as a guide to the installation of the Model GP-2000 Pressure
Reducing Valve. Selection or installation of equipment should always be accompanied by competent technical
assistance. You are encouraged to contact Armstrong International, Inc. or its local sales representative for additional
information.
1. An Armstrong Inverted Bucket Steam Trap is recom-
mended to drain the condensate at the inlet of the
PRV.
2. An Armstrong 100 mesh Y-Strainer should be installed
before the PRV to reduce the chance of dirt fouling.
3. Pressure gauges should be installed before and after
the PRV. The downstream gauge should be installed in
or near the control pipe.
4. Control pipe connections go into ºî tapping on the
side of the pilot valve. Be certain the pipe is pitched
away from the PRV to drain condensate away from
pilot. Erratic control could result if this is not done.
Control pipe length should be a minimum of 10 outlet
pipe diameters from the last tee, elbow or fitting.
Pressure Reducing Valve
Integral and Remote Pilot
Installation, Operation and Maintenance
Minimum of 10 Outlet
Pipe Diameters from
Last Valve or Fitting
By-Pass
Control Pipe
Gate
(Pitch Down)
Valve
GP-2000
Minimum of 20 Outlet
Pipe Diameters from
PRV to First Turn
Note:
Safety Relief Valve to be set at
10 psi higher or 10% higher than
the downstream pressure, whichever
is greater.
Installation Instructions
Model GP-2000
Remote Mount
Globe
Safety Relief
Valve
Minimum of 10 Inlet
Pipe Diameters from
PRV to First Turn
Armstrong
TVS Trap
Note:
Safety Relief Valve to be set at
10 psi higher or 10% higher than
the downstream pressure, whichever
is greater
5. If a bypass line is needed to allow system operation
while the valve is being serviced then install a quality
globe valve on the bypass line. Leaking valves will
cause system problems.
6. Piping immediately downstream of PRV should be
expanded to accommodate low-pressure expansion
through a PRV. Approximately 6,000 ñ 12,000 FPM
maximum velocity.
7. Install the PRV with diaphragm chamber down and
with flow in the direction of the arrow on the body.
8. Do not install a quick opening or quick closing valve on
the downstream side of the PRV. This can cause
erratic pressure control and cause safety relief valves
to discharge.
Minimum of 10 Outlet
Valve
By-Pass
Armstrong
Strainer
GP-2000
Minimum of 20 Outlet
Pipe Diameters from
PRV to First Turn
Armstrong
TVS Trap
Bulletin No. AY-712-C
Pipe Diameters from
Last Valve or Fitting
Safety Relief
Valve