Armstrong Air BCE7E-030 Manuale di istruzioni per l'installazione - Pagina 11

Sfoglia online o scarica il pdf Manuale di istruzioni per l'installazione per Manipolatori d'aria Armstrong Air BCE7E-030. Armstrong Air BCE7E-030 19.

Blower Data

BCE7E-018 Blower Performance
External
Static
Tap 1
Pressure
cfm
in. w.g.
.10
717
.20
596
.30
473
.40
402
.50
358
.60
295
.70
262
.80
N/A
BCE7E-024 Blower Performance
External
Static
Tap 1
Pressure
cfm
in. w.g.
.10
767
.20
662
.30
615
.40
561
.50
522
.60
450
.70
419
.80
365
BCE7E-030 Blower Performance
External
Static
Tap 1
Pressure
cfm
in. w.g.
.10
1061
.20
941
.30
789
.40
640
.50
525
.60
469
.70
434
.80
365
507838-01
Tap 2
watts
cfm
watts
66
707
63
58
570
54
56
430
48
61
335
54
67
302
60
74
248
63
79
202
72
N/A
N/A
N/A
Tap 2
watts
cfm
watts
78
753
75
68
648
66
76
612
77
83
539
83
87
507
89
96
438
93
100
411
103
110
358
108
Tap 2
watts
cfm
watts
115
1104
126
103
973
118
90
848
104
83
789
111
93
728
118
101
629
128
104
581
139
116
521
155
Air Volume and Motor Watts
Tap 3
cfm
watts
735
74
636
70
603
77
540
81
492
92
434
94
399
103
348
108
Air Volume and Motor Watts
Tap 3
cfm
watts
826
88
791
100
750
108
711
116
681
126
628
134
584
142
521
147
Air Volume and Motor Watts
Tap 3
cfm
watts
1169
154
1070
144
1019
151
991
165
946
175
900
181
851
194
754
208
Issue 1813
Tap 4
cfm
watts
cfm
781
81
959
737
91
922
697
101
877
651
105
846
607
117
811
561
121
769
507
131
727
459
137
695
Tap 4
cfm
watts
cfm
957
131
1095
937
142
1063
895
149
1040
861
160
1010
821
172
970
778
175
944
750
186
905
702
194
864
Tap 4
cfm
watts
cfm
1212
166
1278
1157
173
1241
1121
185
1201
1077
199
1169
1038
209
1124
1006
215
1100
956
230
1051
915
237
1000
Tap 5
watts
133
144
150
161
173
179
187
196
Tap 5
watts
189
199
211
226
230
237
248
256
Tap 5
watts
200
210
223
233
244
256
268
275
Page 11 of 19