Distech Controls RS485 UUKL Manuale di installazione - Pagina 4

Sfoglia online o scarica il pdf Manuale di installazione per Unità di controllo Distech Controls RS485 UUKL. Distech Controls RS485 UUKL 4. Option module

Distech Controls RS485 UUKL Manuale di installazione
RS485 Bias Switches
Each RS485 port has an adjacent 3-position biasing switch.
Figure 6: RS485 UUKL module bias switches
Settings of each RS485 bias switch are as follows:
BIA - (Default, middle) RS485 biasing and termination: 2.7K bias
resistors with no termination resistor
END - RS485 biasing and a termination: 562 Ohm bias resistors and
150 Ohm termination resistor
MID - RS485 biasing or termination: 47.5K bias resistors with no
termination resistor
Often, adding RS-485 biasing can improve communications by
eliminating indeterminate idle states.
Typical scenarios for the best RS485 bias switch position are as follows:
BIA - (Default, middle) Often best if the RS485 trunk needs biasing,
but when the EC-BOS-8 UUKL is not installed at the end of the trunk.
END - Often best if the EC-BOS-8 UUKL is installed at the end of an
RS485 trunk of devices that is not already biased.
MID - Often best if the EC-BOS-8 UUKL is put in the middle of an
already-biased RS485 trunk.
If desired, you can change the position of an RS485 port's bias switch
while the EC-BOS-8 UUKL is running.
Each RS485 port also has two LEDs. See "LEDs".
Images are simulated. While all efforts have been made to verify the accuracy of information in this manual, Distech Controls is not responsible for damages or claims arising
from the use of this manual. Persons using this manual are assumed to be trained HVAC specialist / installers and are responsible for using the correct wiring procedures and
maintaining safe working conditions with fail-safe environments. Distech Controls reserves the right to change, delete or add to the information in this manual at any time
Distech Controls, the Distech Controls logo, Open-to-Wireless, EC-Net, Innovative Solutions for Greener Buildings, ECO-Vue, and Allure are trademarks of Distech Controls
Inc. BACnet is a registered trademark of ASHRAE. Echelon, LON, LonTalk, L
4/4
LEDs
Five LEDs are on the front of the Dual RS485 UUKL option module.
LED pairs TX and RX operate as follows:
These LEDs are also visible when the front access door is opened.
Related Documentation
For more information on installing, configuring, and using the EC-BOS-8
UUKL with Dual RS485 option module, refer to the following documents:
©, Distech Controls Inc., 2010 to 2019. All rights reserved.
without notice.
M
and L
ON
ARK
United States and other countries.
Figure 7: LEDs on Dual RS485 option.
COMn (e.g. COM3), TX (Transmit) and RX (Receive).
1
2
COMn+1 (e.g. COM4), TX (Transmit) and RX (Receive).
3
PWR — Green, remains lit while EC-BOS-8 UUKL is
powered.
TX (yellow) — Transmit, flashes when the EC-BOS-8 UUKL is
sending data to a device connected on the RS485 trunk.
RX (green) — Receive, flashes when the EC-BOS-8 UUKL is
receiving data from a device on the RS485 trunk.
EC-BOS-8 UUKL Installation Guide
EC-Net 4 Drivers Guide
W
are registered trademarks of Echelon Corporation registered in the
ON
ORKS
RS485 UUKL_IG_10_EN