esera automation 11228 V2 Manuale d'uso - Pagina 2

Sfoglia online o scarica il pdf Manuale d'uso per Sistemi I/O esera automation 11228 V2. esera automation 11228 V2 7. 8-fold high power switching module / binary output w/auto-e-connect

esera automation 11228 V2 Manuale d'uso
3
Auto-E-Connect® Support
The ESERA Auto-E-Connect® 1-Wire Plug and Play system will be used for the
1-Wire Bus supported. This enables fully automatic configurations of 1-Wire sensors
and actuators on the 1-Wire bus. It is optimized for industrial applications and
enables significant added value beyond the sensor and chip data.
The Auto-E-Connect function automatically recognizes ESERA chips, sensors and actuators, starts suitable
libraries and outputs fully formatted data.
The Auto-E-Connect functionality will be available from mid 2020 via 1-Wire Controllers, 1-Wire Gateways and
1-Wire ECO from ESERA available.
Further information on ESERA Auto-E-Connect can be found on the ESERA website, ESERA Config-Tool 3, or in
the download area for this article in the ESERA Webshop.
4
Technical data
Switching channels:
Switching voltage:
Switching current:
Fuses:
Data interface:
1-Wire device:
Operating voltage:
Current consumpt.12V: idle state, no output relay active: approx. 10mA
All outputs active:
Push-button interface:
Connection:
5
Ambient conditions
Temperature, operation: -20°C to +50°C
Humidity:
Dimensions:
Protection class:
Protection type:
Insulation strength:
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
8, switching relay (NO), separate inputs per channel
10 - 250V DC or AC voltage
Max. 16A for 3 seconds, 10A continuous current per output for resistive load.
For capacitive or inductive loads, appropriate additional circuits, e.g. spark quenching
capacitors, must be provided.
Minimum load 10mA per output
External back-up fuse with 16A recommended
1-wire bus (12V, data and ground),
DS2408 interface (8-fold I/O)
12VDC (+/-10%)
approx. 270mA
8 digital inputs (binary input), pulse input, e.g. for push-button or motion detector (make
contact)
Pulse duration min. 60ms
Input voltage 10-30VDC, max. 10mA per input, common ground.
Inputs isolated from 1-Wire interface and power supply.
The cable length between module and button is not critical, but should not exceed 30m.
screw terminals (up to 2.5qmm cable cross-section)
10 - 92% (non-condensing)
100 x 90 x 70mm (WxHxD)
II
IP20
500VAC output to 1-Wire Bus, 250VAC output to output
11228 V2.0 R1.0 Manual