dixell COOL MATE XLR470 Manuale operativo - Pagina 9
Sfoglia online o scarica il pdf Manuale operativo per Regolatore di temperatura dixell COOL MATE XLR470. dixell COOL MATE XLR470 18. Dual temperature controller
dIXEL
dIXEL
dIXEL
dIXEL
FnC2 Fan operating mode, section 2: C-n = running with the compressor 2, OFF during the defrost; C-y = running with the compressor 2, ON
during the defrost; O-n = continuous mode, OFF during the defrost; O-y = continuous mode, ON during the defrost;
Fnd2
Fan delay after defrost, section 2: (0÷255 min) The time interval between the defrost end and evaporator fans start.
FSt2
Fan stop temperature, section 2: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe 2, above which the fan is
always OFF.
FAP2 Probe selection for fans management, section 2: nP = no probe: fan follows the setting of FnC1 parameter; P1 = thermostat 1 probe; P2
= evaporator 1probe; P3 = thermostat 2 probe; P4 = evaporator 2probe;
ALARMS
ALc1
Temperature alarms configuration, section 1: it determines if alarms are relative to set point 1 or referred to absolute values: rE relative
to set point; Ab absolute temperature
ALU1 Maximum alarm, section 1:
with ALc1=rE: alarm relative to set point1, (0÷50°C) Maximum alarm is enabled when the probe values exceeds the "SET1+ALU" value.
with ALc1=Ab: absolute alarm, (Set1÷Full Sc.) Maximum alarm is enabled when the probe values exceeds the "ALU" value.
ALL1 Minimum alarm, section 1:
with ALc1=rE: relative to set point1, (0÷50°C) this value is subtracted from the set point1. The alarm signal is enabled when the probe
values goes below the "SET1-ALL" value.
with ALc1=Ab absolute value, minimum alarm is enabled when the probe values goes below the "ALL1" value.
ALd1 Temperature alarm delay, section 1: (0÷255 min) time interval between the detection of an alarm condition and the corresponding alarm
signalling.
dAo1 Delay of temperature alarm at start-up, section 1: (0min÷23h 50min) time interval between the detection of the temperature alarm
condition in section after the instrument power on and the alarm signalling.
ALc2
Temperature alarms configuration, section 2: it determines if alarms are relative to set point 2 or referred to absolute values: rE relative
to set point; Ab absolute temperature
ALU2 Maximum alarm, section 2:
with ALc2=rE: alarm relative to set point1, (0÷50°C) Maximum alarm is enabled when the probe values exceeds the "SET2+ALU" value.
with ALc2=Ab: absolute alarm, (Set2÷Full Sc.) Maximum alarm is enabled when the probe values exceeds the "ALU" value.
ALL2 Minimum alarm, section 2:
with ALc2=rE: relative to set point1, (0÷50°C) this value is subtracted from the set point2. The alarm signal is enabled when the probe
values goes below the "SET2-ALL" value.
with ALc2=Ab absolute value, minimum alarm is enabled when the probe values goes below the "ALL2" value.
ALd2 Temperature alarm delay, section 2: (0÷255 min) time interval between the detection of an alarm condition and the corresponding alarm
signalling.
dAo2 Delay of temperature alarm at start-up, section 2: (0min÷23h 50min) time interval between the detection of the temperature alarm
condition in section after the instrument power on and the alarm signalling.
AFH
Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for temperature alarm set point and fan regulation
set point, always positive.
EdA
Alarm delay at the end of defrost: (0
and the alarm signalling.
dot
Delay of temperature alarm after closing the door : (0
door.
doA
Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and its alarm signalling: the flashing message
"dA" is displayed.
PROBE INPUTS
Pbc
Kind of probe: Ptc = PTC; ntc = NTC
oFS1
Thermostat 1 probe calibration (10-11): (-12.0
oFS2
Evaporator 1 probe calibration (8-9): (-12.0
oFS3
Thermostat 2 probe calibration (6-7) : (-12.0
oFS4
Evaporator 2 probe calibration (4-5): (-12.0
P2P
Evaporator 1 probe presence : no= not present: the defrost 1 stops only by time; yES= present: the defrost 1 stops by temperature.
P3P
Thermostat 2 probe presence: no= not present; yES= present.
P4P
Evaporator 2 probe presence : no= not present: the defrost 2 stops only by time; yES= present: the defrost 2 stops by temperature.
DIGITAL INPUTS
i1P
Digital input 1 polarity (1-2):
CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact.
i1F
Digital input 1 operating mode(1-2): configure the digital input function:
MP1 = door switch 1; MP2 = door switch 2, MP: door switch (it's used by both the sections); EA1 = generic alarm section 1; EA2 = generic
alarm section 2; EAL = generic alarm (it's used by both the sections); bA1 = serious alarm mode section 1; bA2 = serious alarm mode
section 2; , bAL = serious alarm mode section (it's used by both the sections); dF1 = Start defrost, section 1; dF2 = Start defrost, section 2;
dEF = Start defrost (it's used by both the sections); oF1 = remote on/ off, section1; oF2 = remote on/ off, section 2; oFF = = remote on/ off
(it's used by both the sections); ES = Energy Saving
i2P
Digital input 2 polarity(2-3):
CL : the digital input is activated by closing the contact;
1592017050 XLR470 GB r1.0 24.05.07.doc
Operating manual
255 min) Time interval between the detection of the temperature alarm condition at the end of defrost
÷
255 min) Time delay to signal the temperature alarm condition after closing the
÷
12.0°C/ -21
21°F) allows to adjust possible offset of the thermostat 1 probe.
÷
÷
12.0°C/ -21
21°F) allows to adjust possible offset of the evaporator 1 probe.
÷
÷
12.0°C/ -21
21°F) allows to adjust possible offsets of the thermostat 2 probe.
÷
÷
12.0°C/ -21
21°F) allows to adjust possible offset of the evaporator 2 probe.
÷
÷
XLR470