dixell COOL MATE XLR470 Manuale operativo - Pagina 9

Sfoglia online o scarica il pdf Manuale operativo per Regolatore di temperatura dixell COOL MATE XLR470. dixell COOL MATE XLR470 18. Dual temperature controller

dixell COOL MATE XLR470 Manuale operativo
dIXEL
dIXEL
dIXEL
dIXEL
FnC2 Fan operating mode, section 2: C-n = running with the compressor 2, OFF during the defrost; C-y = running with the compressor 2, ON
during the defrost; O-n = continuous mode, OFF during the defrost; O-y = continuous mode, ON during the defrost;
Fnd2
Fan delay after defrost, section 2: (0÷255 min) The time interval between the defrost end and evaporator fans start.
FSt2
Fan stop temperature, section 2: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe 2, above which the fan is
always OFF.
FAP2 Probe selection for fans management, section 2: nP = no probe: fan follows the setting of FnC1 parameter; P1 = thermostat 1 probe; P2
= evaporator 1probe; P3 = thermostat 2 probe; P4 = evaporator 2probe;
ALARMS
ALc1
Temperature alarms configuration, section 1: it determines if alarms are relative to set point 1 or referred to absolute values: rE relative
to set point; Ab absolute temperature
ALU1 Maximum alarm, section 1:
with ALc1=rE: alarm relative to set point1, (0÷50°C) Maximum alarm is enabled when the probe values exceeds the "SET1+ALU" value.
with ALc1=Ab: absolute alarm, (Set1÷Full Sc.) Maximum alarm is enabled when the probe values exceeds the "ALU" value.
ALL1 Minimum alarm, section 1:
with ALc1=rE: relative to set point1, (0÷50°C) this value is subtracted from the set point1. The alarm signal is enabled when the probe
values goes below the "SET1-ALL" value.
with ALc1=Ab absolute value, minimum alarm is enabled when the probe values goes below the "ALL1" value.
ALd1 Temperature alarm delay, section 1: (0÷255 min) time interval between the detection of an alarm condition and the corresponding alarm
signalling.
dAo1 Delay of temperature alarm at start-up, section 1: (0min÷23h 50min) time interval between the detection of the temperature alarm
condition in section after the instrument power on and the alarm signalling.
ALc2
Temperature alarms configuration, section 2: it determines if alarms are relative to set point 2 or referred to absolute values: rE relative
to set point; Ab absolute temperature
ALU2 Maximum alarm, section 2:
with ALc2=rE: alarm relative to set point1, (0÷50°C) Maximum alarm is enabled when the probe values exceeds the "SET2+ALU" value.
with ALc2=Ab: absolute alarm, (Set2÷Full Sc.) Maximum alarm is enabled when the probe values exceeds the "ALU" value.
ALL2 Minimum alarm, section 2:
with ALc2=rE: relative to set point1, (0÷50°C) this value is subtracted from the set point2. The alarm signal is enabled when the probe
values goes below the "SET2-ALL" value.
with ALc2=Ab absolute value, minimum alarm is enabled when the probe values goes below the "ALL2" value.
ALd2 Temperature alarm delay, section 2: (0÷255 min) time interval between the detection of an alarm condition and the corresponding alarm
signalling.
dAo2 Delay of temperature alarm at start-up, section 2: (0min÷23h 50min) time interval between the detection of the temperature alarm
condition in section after the instrument power on and the alarm signalling.
AFH
Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for temperature alarm set point and fan regulation
set point, always positive.
EdA
Alarm delay at the end of defrost: (0
and the alarm signalling.
dot
Delay of temperature alarm after closing the door : (0
door.
doA
Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and its alarm signalling: the flashing message
"dA" is displayed.
PROBE INPUTS
Pbc
Kind of probe: Ptc = PTC; ntc = NTC
oFS1
Thermostat 1 probe calibration (10-11): (-12.0
oFS2
Evaporator 1 probe calibration (8-9): (-12.0
oFS3
Thermostat 2 probe calibration (6-7) : (-12.0
oFS4
Evaporator 2 probe calibration (4-5): (-12.0
P2P
Evaporator 1 probe presence : no= not present: the defrost 1 stops only by time; yES= present: the defrost 1 stops by temperature.
P3P
Thermostat 2 probe presence: no= not present; yES= present.
P4P
Evaporator 2 probe presence : no= not present: the defrost 2 stops only by time; yES= present: the defrost 2 stops by temperature.
DIGITAL INPUTS
i1P
Digital input 1 polarity (1-2):
CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact.
i1F
Digital input 1 operating mode(1-2): configure the digital input function:
MP1 = door switch 1; MP2 = door switch 2, MP: door switch (it's used by both the sections); EA1 = generic alarm section 1; EA2 = generic
alarm section 2; EAL = generic alarm (it's used by both the sections); bA1 = serious alarm mode section 1; bA2 = serious alarm mode
section 2; , bAL = serious alarm mode section (it's used by both the sections); dF1 = Start defrost, section 1; dF2 = Start defrost, section 2;
dEF = Start defrost (it's used by both the sections); oF1 = remote on/ off, section1; oF2 = remote on/ off, section 2; oFF = = remote on/ off
(it's used by both the sections); ES = Energy Saving
i2P
Digital input 2 polarity(2-3):
CL : the digital input is activated by closing the contact;
1592017050 XLR470 GB r1.0 24.05.07.doc
Operating manual
255 min) Time interval between the detection of the temperature alarm condition at the end of defrost
÷
255 min) Time delay to signal the temperature alarm condition after closing the
÷
12.0°C/ -21
21°F) allows to adjust possible offset of the thermostat 1 probe.
÷
÷
12.0°C/ -21
21°F) allows to adjust possible offset of the evaporator 1 probe.
÷
÷
12.0°C/ -21
21°F) allows to adjust possible offsets of the thermostat 2 probe.
÷
÷
12.0°C/ -21
21°F) allows to adjust possible offset of the evaporator 2 probe.
÷
÷
XLR470
cod. 1592017
cod. 1592
cod. 1592
cod. 1592
017050
017
017
050
050
050
9/18