3HS RMS-D II Manuale di installazione - Pagina 8

Sfoglia online o scarica il pdf Manuale di installazione per Allarme fumo 3HS RMS-D II. 3HS RMS-D II 13. Ceiling mounted visual smoke detector

Installationshandbuch RMS-D II und RMS-V II

Mounting the RMS-D II

The in-wall socket holds the smoke detector casing in the ceiling and is mounted with two clamping screws
in the ceiling. Spring steel elements are used to hold the RMS-D ll in the in-wall socket and allow for an
easy mounting and removal.
The smoke detector must be mounted on a stable structure. Dust and other impurities must be
-
removed from the ceiling before the smoke detector can be replaced.
Drill a round hole with a 75mm diameter and at least 100mm deep in the ceiling. Please note that
-
the in-wall socket can only be fastened in a hole with a 75mm diameter.
Pull the wire through the in-wall socket and fasten the socket to the ceiling using both of the
-
clamping screws. The clamping range is between approximately 5mm and 40 mm.
Connect the wire with the smoke detector in accordance with the installation plan in Fig. 2. and
-
insert the smoke detector into the in-wall socket.
Remove the protective foil from the smoke detector before turning on the voltage supply.
-
Installationshandbuch: RMS-D II und RMS-V II Relais
®3HStrading GmbH&Co.KG, Königsheimer Strasse 13,
D-78603 Renquishausen, Tel. 07429 33 61 Fax. 07429 91 61 335,
www.3HS.de
Seite 8 von 13
Stand: 01.12.2015
Version:2.7