Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper
voltage level (Output Voltage and Stand-by Specification Charts, pg. 4).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at
the battery terminals and at the board terminals marked [– BAT +] to ensure that there is no break in the bat-
tery connection wires.
Note:
AL300XB2V, AL400XB2V, AL600XB220 and AL1012XB220 (Power Supply Board) maximum
charge current is 0.7A.
AL1024XB2V (Power Supply Board) maximum charge current is 3.6A.
Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary.
Power Supply Board
LED
Red (DC)
ON
ON
OFF
OFF
Red (Bat)
ON
OFF
MOM5 - Output Module
LED
Power (Green)
Trigger (Green)
Outputs (Red)
- 4 -

LED Diagnostics:

Green (AC)
ON
OFF
ON
OFF
Battery Status
Normal operating condition.
Battery fail/low battery.
ON
Normal operating condition.
Input is triggered (alarm condition).
Output tripped due to a short circuit or
overload condition.

Maintenance:

Power Supply Status
Normal operating condition.
Loss of AC. Stand-by battery supplying power.
No DC output. Short circuit or thermal overload condition.
No DC output. Loss of AC. Discharged battery.
OFF
Power failure.
No input trigger (non-alarm condition).
Normal operation.
M220 Series