input DC voltage is higher than 16V(32V/62V). The buzzer will whistle
continuously and the green light is off, red light is on. Please turn off the
inverter and adjust the input voltage to the admissible range.
4. Overload protection: The inverter will automatically shut down when the load is
higher than the rated power. The buzzer will whistle continuously. Turn off the
inverter and resume to normal operation after taking away the excessive load.
5. Short-circuit protection: The AC output will be automatically shut down when
short circuited. It will automatically reset after the problem is solved.
6. Thermal protection: The unit will get hot during operation. If the temperature is
higher than 149°F, the inverter will automatically shut down. Then the buzzer
will whistle continuously and the green light is off, red light is on. Please turn
off the inverter, and continue using it after the temperature goes back to
normal naturally. Meanwhile find out the factors causing the fault, such as
ventilation, ambient temperature, vent, load power etc. It can avoid similar
things from happening again.
**NOTE** The numbers in the parenthesis are for 24V and 48V models. In the case of
over voltage, under voltage and thermal protection, the inverter will shut down. When
the inverter is in the OFF position, the inverter doesn't consume battery current.
HI-POT TESTING OF DC to AC Inverter
Most of our AC inverters are Listed by Intertek to conform to UL 458 One of the
requirements of UL 458 is that all AC inverters pass a High Voltage Dielectric Withstand
Test, commonly called the Hi-Pot Test. The voltage applied to the control is usually
equal to 1,000 volts, plus two times the line voltage rating of the inverter. Therefore, the
standard hi-pot voltage for 115 VAC inverter is 1,250 VAC. For 230 VAC or dual voltage
inverters, the hi-pot voltage is 1,500 VAC. This Aims power inverter is hi-pot tested
before it leaves the factory, with a UL Certified hi-pot tester, set to the voltages shown
above.
For UL Listed equipment, UL requires that customers perform a final Hi-Pot test of their
machine with the AC inverter installed. Hi-Pot testing is used to detect any electrical
leakage between live metal components and the frame of the machine that is connected
to earth ground. This helps prevent electrical shock to the user of the equipment should
a live component touch the frame and the user touch the frame and ground at the same
time.
(CAN/CSA-C22.2 No. 107.1) and are identified with the cETL Listed Mark.