Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Sensor identifies bright, light off (dependent upon operating mode)
Not illuminated
Sensor identifies dark, light on (dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for commands from the remote control
Illuminated for 1 seconds
Signal validly received
Illuminated for 0.25 seconds
Not-accepted command, sensor blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when an attempt is made to set a twilight-value that is too high or
too low
Red LED as an acknowledgement of receipt for commands from the remote control
Red and green LEDs flash 3x briefly every 5 seconds
Indicates semi-automatic mode
Red and green LEDs light up alternately
Determining the light value for automatic shutdown with sufficient daylight. (This is only indicated with a set lag
time of 30 minutes.)
11.
Maintenance
For the maintenance of the AR-024 occupancy sensor the requirements as stated in EN 60079-17 apply. If the
occupancy sensor or the connection cable is no longer in good condition, very dirty or damaged, it must be repaired or
cleaned immediately. The power supply to the occupancy sensor must be switched off and may only be restored after
the maintenance has been carried out and approved.
The advised maintenance cycle for this occupancy sensor depends on its specific use and must therefore be agreed
upon with the user for the expected use.
12.
Repair
If repairs are carried out in an incompetent manner, the explosion-safety of the occupancy sensor can no longer be
guaranteed. Therefore it is preferred that the occupancy sensor is returned to the manufacturer for repair.
13.
Removal / re-use
The equipment can be completely processed as electronic waste. For processing regarding disposal or reuse of the
product and its packaging, national disposal and environmental laws and legislation must be taken into consideration.