Altronix ACM Series Manuale di installazione - Pagina 10

Sfoglia online o scarica il pdf Manuale di installazione per Controllore Altronix ACM Series. Altronix ACM Series 13. Access power controllers with power supplies

Altronix ACM Series Manuale di installazione
AL1024ULACM Battery Size Calculation Worksheet:
A. AL1024ULACM internal current consumption
B. Load current consumption
C. Stand-by time required (Hours)
D. Battery capacity required for stand-by
E. AL1024ULACM internal power consumption
F. Load current consumption
G. Alarm duration (Hours, example: 15 Min. = 0.25 Hour)
H. Battery capacity required for Alarm
I. Total calculated battery capacity
J. Battery capacity required
Note: AL1024ULACM power supply is designed to work with batteries up to 65AH. Please note, line [I]
must not exceed 36AH. You have to reduce either stand-by current consumption or stand-by time in
order to comply with requirement.
To determine actual battery size please round line [J] to the nearest larger standard battery size.
- 10 -
(stand-by)
(stand-by)
(A+B)*C
(Alarm)
(Alarm)
(Alarm)
(E+F)*G
D+H
I*1.8 (safety factor)
__________
0.35A
__________
A
__________
H
__________
AH
__________
0.35A
__________
A
__________
H
__________
AH
__________
AH
__________
AH
ACM Series