Altronix AL1002ULADA Manuale di applicazione - Pagina 5

Sfoglia online o scarica il pdf Manuale di applicazione per Estensore Altronix AL1002ULADA. Altronix AL1002ULADA 8. Nac power extenders
Anche per Altronix AL1002ULADA: Manuale di installazione (13 pagine), Manuale di installazione (17 pagine), Manuale di applicazione (8 pagine), Manuale di applicazione (8 pagine)

Altronix AL1002ULADA Manuale di applicazione
Function
Input to Output
Follower Mode
Temporal Code 3 Mode
Steady Mode
For the above modes DIP Switch 4 determines which Input controls the
corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by Input 1.
Switch 4 in the OFF position causes output(s) to be controlled by Input 2.
Function
Amseco
Sync Mode*
®
Gentex
Sync Mode*
Gentex is a registered
trademark of
Gentex Corporation.
System Sensor
®
Sync Mode*
System Sensor is a
registered trademark of
Honeywell.
CooperWheelock
®
Sync Mode*
CooperWheelock is a
registered trademark of
Cooper Wheelock.
*Note: AL602ULADA, AL602ULADAJ, AL802ULADA, AL802ULADAJ, AL1002ULADA,
AL1002ULADAJ and R1002ULADA will only synchronize horns, horn/strobes and strobes that contain
synchronization capability. The same synchronization mode must be selected for all outputs.
02 ULADA Application Guide
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Switch Positions
ON
OFF
1
2, 3
3
1, 2
1, 2, 3
Sync Mode Selection Table:
Switch Positions
ON
OFF
1, 3,
2
4
1, 2,
3, 4
1, 2, 4
3
2, 3, 4
1
Descriptions
Output follows signal it receives from the corresponding
input (i.e. FACP Sync module - maintains synchronization
of notification appliance circuit).
Enables Temporal Code 3 signal generation output.
This mode will accept a steady or a pulsing input.
A steady output signal will be generated.
This mode will accept steady or pulsing input.
Descriptions
This mode is designed to work with the Amseco series of horns,
strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the flash timing of the
strobe, and allowing audible notification appliances (horns) and
visual notification appliances (strobes) to be silienced/ deactivated
at the same time.
This mode is designed to work with the Gentex
strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the flash timing of the
strobe, and allowing audible notification appliances (horns) and
visual notification appliances (strobes) to be silienced/ deactivated
at the same time.
This mode is designed to work with the System Sensor
horns, strobes, and horn/strobes to provide a means of synchroniz-
ing the Temporal-coded horns, synchronizing the one-second flash
timing of the strobe, and allowing audible notification appliances
(horns) and visual notification appliances (strobes) to be silienced/
deactivated at the same time.
This mode is designed to work with the CooperWheelock series of
horns, strobes, and horn/strobes to provide a means of synchroniz-
ing the Temporal-coded horns, synchronizing the one-second flash
timing of the strobe, and allowing audible notification appliances
(horns) and visual notification appliances (strobes) to be silienced/
deactivated at the same time.
AL800LGK9E Board
Output DIP Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
®
series of horns,
®
series of
- 5 -