Config
y CURRENT LEVEL: Displays the current
level of the ballast
- LEFT or RIGHT to select ballast
y MAX LEVEL: The maximum level of the
ballast
- LEFT or RIGHT to select ballast
- UP or DOWN to select the maximum
value
- YES (and hold) to confirm change
- NO to cancel request
y MIN LEVEL: The minimum level of the
ballast
- LEFT or RIGHT to select ballast
- UP or DOWN to select minimum value
- YES (and hold) to confirm change
- NO to cancel request
y ON LEVEL: The ballast on level (turn on
level)
- LEFT or RIGHT to select ballast
- UP or DOWN to select value
- YES (and hold) to confirm change
- NO to cancel request
y FAILURE LEVEL: The level the ballast
uses in case of DALI failure
- LEFT or RIGHT to select ballast
(Note: Dali-Scope does not allow this value
to be changed)
y FADE RATE: The ballast fade rate (as set
in the DALI specification)
- LEFT or RIGHT to select ballast
- UP or DOWN to select value
- YES (and hold) to confirm change
- NO to cancel request
y FADE TIME: The time of the fade
- LEFT or RIGHT to select ballast
- UP or DOWN to select value
- YES (and hold) to confirm change
- NO to cancel request
Dali-Scope User Guide
y RESET: Reset the Ballast Properties
- UP or DOWN to select ballast
- YES (and hold) to confirm change
- NO to cancel request
(Note: This will reset the ballast properties,
except channel address)
Advanced Config
This menu is activated by holding the CONFIG
key for 2 seconds. Use the CONFIG button to
select between the different sub-menus. The
options are:
y POWER OFF TIMER: [Always On] [3 Min]
[10 Min] - Use UP & DOWN to adjust
y SCROLL SPEED: (Variable) - Use UP &
DOWN to adjust
y BRIGHTNESS: [Normal] [Bright] - Use UP
& DOWN to adjust
y MAN TEST: (Display and keyboard test
used in manufacture) - All keys are used
for testing
To leave ADVANCED CONFIG press and
hold the CONFIG button for 2 seconds.
Dali-Scope Specification
Mechanical
Housing: Hand-held case
Material: ABS 94HB Plastic, UL94MB Fire-rated
Overall Dimensions: 95mm (H) x 65mm (W) x
28mm (D)
Weight: 0.1kg
Country of Manufacturer: UK
Electrical
Input Voltage: 2 x AA Battery
Duty Cycle: 80% @ 25°C
Environmental
Operating Temperature: 0°C to 40°C
Storage Temperature: -10°C to +50°C
Operating Relative Humidity (max): 80% Non-
Condensing
IP Rating: IP20 Indoor Use Only
Certification: CE FCC, WEEE, RoHS
Warranty: 2 Year (Return to Base)
Page 7