Alula RE614 Manuale di avvio rapido - Pagina 2
Sfoglia online o scarica il pdf Manuale di avvio rapido per Allarme fumo Alula RE614. Alula RE614 12. Smoke alarm connect+ compatible
Normal Operation
Power Up
Standby
Sensing Fire
Fault Mode
Low Battery
Faulty Smoke Sensor
Faulty Heat Sensor
End of Life
Silence Sounding
Alarm
Silence "End of Life"
indication (up to
30 days)
Test Mode
Test Smoke Alarm
Alarm Memory
24 Hour Memory
Long Term Memory
1.1. Normal Operation
1.1.1. Power Up
Twist off the Alarm from the mounting
plate (see Quick Start Guide). Remove the
battery tab to power the Alarm, the red
LED will flash once followed by one flash of
the yellow LED to indicate that the Alarm
has been powered successfully and is now
in standby mode.
1.1.2. Standby
In standby mode there are no active
visible or audible indications which can be
intrusive to the householder. To confirm
that the Alarm is operational perform a
weekly button test.
1.1.3. Weekly button test
Press and hold the test button and verify
that the red LED flashes rapidly and the
Alarm ramps up to full sound.
1.1.4. Sensing Fire
As soon as the Alarm senses smoke it will
go into Alarm. The red LED on the Alarm
sensing smoke flashes rapidly to indicate
this is the Alarm sensing smoke / fire.
Follow the instruction in section 3 and
evacuate the building.
1.1.5. Silence False / Nuisance alarm
Occasionally Smoke Alarms can be
activated by phenomena other than fire,
e.g. dust, insects, cooking fumes. Once
you are sure it is a nuisance alarm press
the large test button to silence the Alarm
for 10 minutes – the red LED will then
flash every 8 seconds for 10 minutes.
Indicator Summary
Action
Insert Batteries
Action
Press & Release Button
Press & Release Button
Action
Press Button
Action
Press & Hold Button
Red LED
1 Flash
Off
Rapid Flashing
Red LED
Off
Off
Off
Off
1 Flash every 8 sec
Off
Red LED
Rapid Flashing
Red Led
2 Flashes every 48
sec for 24 hours
Rapid Flashing
1.2. Fault Conditions
1.2.1. Low battery
The Alarm will emit a short beep and flash
the Yellow LED when it becomes partially
depleted. Check the date when the Alarm
should be replaced which is given on the
sidewall of the Alarm. When electronic
self testing indicates that the battery is
becoming low the Alarm will beep and
the yellow LED will flash at the same time
(about every 48 seconds) to warn the user.
This indicates that the batteries must be
replaced.
1.2.2. Contaminated chamber
If the Alarm sounds without any apparent
smoke being present, press the test
button to silence the Alarm for 10 minutes
(as described in 1.1.5 above). If the Alarm
sounds again it may be contaminated.
Pressing the test button again, within 4
minutes of the Alarm re-sounding, will
get the Alarm to compensate for chamber
contamination. This will normally resolve
the problem.
If the Alarm re-sounds for a third time, the
Alarm is excessively contaminated and
must be replaced. If it is not convenient
to replace it immediately, pressing the
test button within 4 minutes of it going
into alarm (for the third time) will silence
the Alarm for 8 hours – however it will
give two short beeps (second apart) every
10 minutes to remind the user it has been
disabled. If the contamination clears the
2
Yellow LED
1 Flash
Off
Off
Yellow LED
1 Flash every 48 sec
2 Flashes every 48 sec
2 Flashes every 48 sec
3 Flashes every 48 sec
Off
Off for 72 hours
Yellow LED
Off
Yellow LED
Off
Off
Sounder
Off
Off
Full Sound
Sounder
1 Beep
2 Beeps
2 Beeps
3 Beeps
Off for 10 mins
Off for 72 hours
Sounder
Full Sound
Sounder
Off
Rapid Chirping