Operation:
Ensure that the blades open and close properly while running the damper through its full cycle. Check
for slack linkage, especially at the actuator, if there is a problem. Tighten the linkage as required.
Closure:
Remove any unnecessary objects that could hinder blade closure or appropriate blade-to-blade or
blade-to-frame seal.
Moving Parts:
Monitor those elements that are supposed to move freely, such as linkages, bearings, and blades, can.
Lubricating these components helps to keep them from rusting and accumulating unnecessary friction
over time. Only use Moli-spray oil or a related graphite-based dry lubricant since regular lubricating oil
attracts dirt more easily. When using ball bearings (without grease fittings) and synthetic, oil-
impregnated bearings lubrication is not necessary.
Foreign Matter:
Dirt and dirt can build up over time on damper surfaces. Wipe the damper surfaces with a non-oil-based
mild solvent/cleaner to avoid impeding airflow and buildup of debris.
Damper Trouble Shooting:
The following is a cause and correction list for common concerns regarding damper operation:
Symptom
Damper fails to fully
open and/or fully
close
Actuator runs hot or
makes a humming
noise
Alumavent warrants this equipment to be free from defects in material and workmanship for a
period of one year from the purchase date. Any units or parts which prove to be defective during
the warranty period will be repaired or replaced at our option. Alumavent shall not be liable for
damages resulting from misapplication or misuse of its products. Alumavent will not be responsible
for any installation or removal costs. Alumavent will not be responsible for any service work or back
charges without prior written authorization.
Possible cause
Frame is cracked/out of square
causing blades to bind on jamb seals
Linkage on actuator is loose
Defective actuator
Screws in damper linkage
The linkage of the actuator is hitting
the wall or floor
Contaminants on damper
Actuator prohibited from reaching
end of stroke
Adjust frame so that it is square and plumb
Close damper, disconnect power, adjust
Locate screws and remove or relocate
Damper installed too far into wall. Move
jackshaft, open damper, power actuator to
end of spring, tighten linkage. Verify
Warranty
Corrective Action
within the duct/opening
and tighten linkage
Replace actuator
out
Clean with a non oil-based mild
solvent/cleaner
Disconnect linkage from
amperage draw
pg. 6