AKO AKO-D14023 Manuale di istruzioni per l'installazione - Pagina 2

Sfoglia online o scarica il pdf Manuale di istruzioni per l'installazione per Regolatore di temperatura AKO AKO-D14023. AKO AKO-D14023 6.

AKO AKO-D14023 Manuale di istruzioni per l'installazione
5.2- Setting parameters
Programming Menu (parameters)
After 20 seconds with no key being pressed, the equipment will return to the previous level. If you are on level 3, the changes will not be saved
3 KEY EQUIPMENT
OUT OF
PROGRAMMING
PROGRAMMING
20 sec.
Change
10 sec.
Menu
SET
Temperature
Level 1
Indication
Menu
OK
OK
SET
SET
Change set point (only equipment with three keys)
5 sec.
SET
Current
Temperature
Value
Indication
6- Table of parameters and messages
Def. column shows factory-set default parameters. Those marked with * are variable parameters depending on the application chosen in the wizard or the P3 parameter (see table "Default
parameters by application"). Unless otherwise stated, temperatures are expressed in °C. (Equivalent velues in °F)
AKO-D14023-C
AKO-D14012, AKO-D14023, AKO-D14024
AKO-D14120, AKO-D14123, AKO-D14124, AKO-D14125
Menus and description
Level1
rE
Level 2
Control
Level 3
Description
Temperature Adjustment (Set Point)
SP
(limits depending on probe type)
C0
Calibrating probe 1 (Offset)
C1
Probe 1 differential (Histeresis)
Upper blocking of the set point
C2
(cannot be set above this value)
C3
Lower blocking of the set point (cannot be set below this value)
Type of delay for protection of the compressor:
C4
0=OFF/ON (since the last disconnection); 1=ON (since start-up/reset);
2=OFF-ON/ON-OFF (since the last shut-down /start-up)
C5
Protection delay time (value of the option selected in parameter C4)
Status of COOL relay with probe fault
C6
0=OFF; 1=ON; 2=Average based on last 24 hours prior to probe fault;
3=ON-OFF as prog. C7 and C8 (in heat mode always OFF)
Time relay ON in case of faulty probe
C7
(If C7=0 and C8¹0, the relay will always be OFF deenergised)
Time relay OFF in case of fault of probe 1
C8
(If C8=0 and C7¹0, the relay will always be ON energised)
EP
Exit to Level 1
Level 2
DEFROST Control (if P0=0 Direct, Cold)
dEF
Level 3
Description
Defrost frequency
d0
(Time between two starts)
d1
Maximum defrost duration (0=defrost deactivated)
Type of message during defrost:
d2
0=Current temperature; 1=Temperature at start of defrost;
2=Display dEF message
Maximum duration of message
d3
(time added at the end of the defrost)
Calculated time between defrost periods:
d8
0=Total actual time; 1 =Sum of times the compressor is on
EP
Exit to Level 1
CnF
Level 2
General status
Level 3
Description
P0
Type of operation 0=Direct, Cold;1=Inverted, Heat
P1
Delay of all functions on receiving electrical power
Access code (password) functions
P2
0=Inactive; 1=Block access to parameters; 2=Keyboard lock
Set the default parameters according to the type of application (see accompanying table)
1=Multipurpose
2=Frozen
P3
4=Fresh Fish
5=Soft Drinks
7=AC
8=Heat/Incubators
P5
Address (only systems with built-in communications)
Temperature display mode
0= Integer °C
P7
2=Integer °F
P9
Selection of probe type 0=NTC; 1=PTC
EP
Exit to Level 1
tid
Nivel 2
Level 2
Control Acceso e Información
Access and information control
Description
Level 3
Nivel 3
Descripción
L5
Access code (Password)
PU
Program version (Information)
Pr
Program revision (Information)
EP
Exit to Level 1
EP
Exit Programming
20 sec.
20 sec.
Change
param.
OK
OK
SET
SET
Level 2
Level 3
Parameters
Values
Change
Accept value
value
and Esc.
SET
Temperature
New
Value
Indication
Values Min. Def. Max.
With NTC
-50
(ºC/ºF)
(-58ºF)
With PTC
(ºC/ºF)
-20.0
(ºC/ºF)
0.1
With NTC
(210ºF)
(ºC/ºF)
C3
With PTC
-50
(ºC/ºF)
(-58ºF)
(-58ºF)
0
(min.)
0
0
(min.)
0
(min.)
0
Values Min. Def. Max.
(h.)
0
(min.)
0
0
(min.)
0
0
Values
Min. Def. Max.
0
(min.)
0
0
3=Fruit and Vegetables
1
6=Bottle Racks
1
1=One decimal in ºC
0
3=One decimal in °F
0
Min. Def. Max.
Valores Mín. Def. Máx.
Values
0
1 KEY EQUIPMENT
OUT OF
PROGRAMMING
Change
value
10 sec.
OK
SET
SET
Temperature
Indication
OK
SET
> 5sec.
WARNING: The default parameters by type of application have been defined for the
most common applications. Check that these parameters are suitable for your
installation.
DEFAULT SETTINGS BY APPLICATION (P3)
1
99
·
Multipurpose
(210ºF)
150
-
·
SP
2 (35,6ºF)
(302ºF)
d0
4
·
· ·
0.0
20.0
d1
20
·
2.0
20.0
P0
0
99
99
·
(210ºF)
150
MESSAGES
-
·
(302ºF)
L5
Access code (Password) request
-50
·
C2
dEF
Indicates a defrost is underway. (Only if parameter d2=2)
Probe 1 faulty (open circuit, crossover, NTC: temp. >110°C or <-55 °C
E1
·
PTC: temp. >150 °C or <58 °C) - (equivalent limits in °F)
0
2
D: Displays the message on the display
·
0
120
S: Shows the message in the AKO-5004 software (Only AKO-D14023-C)
·
0
3

7- Technical specifications

·
10
120
AKO-D14023/D14024/D14123/D14124/D14125 . 230 V~ ±10 % 50/60 Hz 3.5 VA
Power supply
AKO-D14120. . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 V~ +8 % - 12 % 50/60 Hz 4 VA
·
5
120
AKO-D14023-C. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
·
· ·
AKO-D14012 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maximum Voltage SELV circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 V
Comunication (Only AKO-D14023-C). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modbus RTU RS485
·
96
Inputs (According to P4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 NTC/PTC
·
255
Relay COOL 16 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (EN60730-1: 12(9) A 250 V~)
Number of relay operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN60730-1: 100.000 operations
·
2
2
Types of probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NTC AKO-149xx / PTC AKO-1558xx
Measurement range NTC. . . . . . . . . . . . . . . . . . . . . . . . . . . . -50,0 ºC to +99,9 ºC (-58,0 ºF to 211 ºF)
·
5
255
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0,1 ºC
·
0
1
Working environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -10 to 50 ºC, humidity <90 %
·
Ambient storage humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 to 70 ºC, humidity <90 %
Class of protection - front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP65
Fixation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Panel-mounted with anchors
·
1
Panel cutout dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 x 29 mm
·
0
255
Front panel dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 x 38 mm
·
· ·
0
2
Depth
AKO-D14023-C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 mm
Other models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 mm
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Screw terminals for cables up to 2.5 mm²
·
-
8
Rating of control device: built-in, automatic operation feature Type 1.B, for use in clean environments,
Class A software and continuous operation. Pollution classification 2 s/ UNE-EN 60730-1.
·
·
·
1
255
Double insulation between supply, secondary circuit and relay output.
Rated pulse voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2500 V
·
· ·
1
3
Temperature during ball-pressure test
·
· ·
0
1
·
· ·
Voltage and current as per EMC tests
·
· ·
-
99
-
·
· ·
-
·
· ·
Current of radio jamming supression tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270 m
·
· ·
·
· ·
PROGRAMMING
20 sec.
20 sec.
Change
Change
param.
Menu
OK
SET
SET
< 5sec.
> 5sec.
< 5sec.
Level 1
Level 2
Menu
Parameters
OK
SET
SET
SET
Key pressed
Key pressed
> 5sec.
several times
several times
2
3
4
5
Frozen
Fruit and
Fresh Fish
Soft Drinks
Vegetables
-18 (-0,4ºF)
10 (50ºF)
0 (32ºF)
3 (37,4ºF)
4
4
4
24
20
20
20
20
0
0
0
0
PTC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . -50,0 ºC to +150 ºC (-58,0 ºF to 302 ºF)
Accessible parts . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 ºC
Parts which position active elements . . . . . . . . . . . . 125 ºC
AKO-D14023/D14023-C/D14024/
AKO-D14123/D14124/D14125/ . . . . . . . . . 207 V, 17 mA
AKO-D14120 . . . . . . . . . . . . . . . . . . . . . . . . 105 V, 36 mA
AKO-D14012 . . . . . . . . . . . . . . . . . . . . . . . 9,6 V, 181 mA
User Manual available at www.ako.com
20 sec.
Change
OK
value OK
SET
SET
SET
SET
> 5sec.
< 5sec.
> 5sec.
Level 3
Values
6
7
8
Bottle Racks
AC
Heat/
Incubators
12 (53,6ºF)
21 (69,8ºF)
37 (98,6ºF)
-
24
96
20
0
-
0
0
1
D
D
-
D
S
90-260 V ~
50/60 Hz 6 VA
~
12/24 V –
±20% 2.5 VA
A