AKO 52068 Manuale - Pagina 10
Sfoglia online o scarica il pdf Manuale per Sistema di sicurezza AKO 52068. AKO 52068 12.
Wiring
Always disconnect the power supply before making any connections.
The power supply circuit should be connected with a minimum 2 A, 230 V, switch located close to the unit. Power
supply cables should be H05VV-F or H05V-K. The gauge will depend on local regulations, but should in no case be
2
less than 1 mm .
Cables for connecting the relay contact should have a sufficient gauge for the equipment to be connected.
For connecting the pushbutton, use a V3V3-F type cable with three 0,5 mm wires minimum and an insulation
voltage of 300/500 V. The maximum distance is 100 m.
AKO-52067
ALARM STATION
BASIC
PUSHBUTTON
AKO-52068
ALARM STATION
BASIC
PUSHBUTTON
Power supply connection
and alarm output
8A
1
2
3
4
5
C
NO
NC
230 Vac
ALARM
Input
output
Max. 100 mts
Power supply connection
and alarm output
8A
1
2
3
4
5
C
NO
NC
230 Vac
ALARM
Input
output
Max. 100 mts
Cable not
included
Jumper wire necessary
10
2
Pushbutton
input
6
7
8
Cable not
included
Pushbutton
input
6
7
8
5206H701 Ed.03
+12Vcc
GND