docherty SEVERN CORNER Manuale di installazione - Pagina 5
Sfoglia online o scarica il pdf Manuale di installazione per Camino da interno docherty SEVERN CORNER. docherty SEVERN CORNER 14.
3.2 Floor protection
Unless the fireplace is installed on a 100% non-flammable floor it will be necessary to stand
the appliance on a non-combustible base of at least 12mm thick and able to withstand the
weight of the appliance and finished construction. It should extend 800mm in front of the
appliance and 400mm to sides and rear of the appliance. However if the floor area is larger
than this it would be good practice to cover the entire internal floor area of the enclosure.
The surface temperature of the finished floor should not exceed 85 deg. C when in normal
operation, otherwise a constructional hearth of 125mm thick will be required. There is a risk
of increased temperatures if correct levels of ventilation are not achieved.
3.3 Chimney fire prevention measures:
Ordinary operation, especially with humid fuel, leads to the settling of ash and tar in the
chimney. Neglecting regular checking and cleaning of the chimney in accordance with Building
Regulations increases the danger of fire. We recommend that the chimney should be swept
twice a year.
In case of ash or tar catching fire in the chimney, please follow this procedure:
• do not under any circumstances extinguish the fire with water as it would create an
abnormal amount of steam and subsequently rip the chimney open
•
if possible, the combustion chamber should be covered with dry sand, which will extinguish
the fire
• close all intakes of air for combustion; if possible, cover the chimney. However, the smoke
must not accumulate back in the house
• contact your nearest fire fighting brigade to assess the situation and the necessity to
report it as a fire fighting emergency
• do not leave the house until the chimney is burned up; regularly check the chimney
temperature and the course of combustion
• contact a chimney service engineer before starting a new fire in the stove to assess the
state of the chimney and also contact the manufacturer of the fireplace stove for inspection.
4. Assembly regulations
4.1 General
The fireplace insert must be installed on the appropriate stand supplied by the manufacturer
or on a brick pedestal on floors with an appropriate load capacity. In case of fireplace inserts
with an enclosure, it is necessary to also consider the weight of the enclosure! If the existing
arrangement does not meet this basic requirement, necessary steps must be taken (e.g.
using a floor plinth/hearh for distributing the load). Make sure that there is enough space for
cleaning the fireplace insert, connecting flue pipes and the chimney unless the chimney can
be cleaned from other method, e.g. cleaning access door designed for this purpose.
4.2 Chimney connection
Before assembling the closed fireplace insert it is necessary to calculate that the chimney
construction will be suitable for the installed fireplace insert nominal output as far as design,
vent size and effective height are concerned.
A suitable chimney (minimum profile, chimney draft, tightness, etc.) is a basic condition for
the proper functioning of the fireplace inserts. You should therefore contact an approved
installer before installing the fireplace insert. Chimney values are included in the attached
technical sheet. A smoke shutter or a draft regulator should be installed for chimneys with
too strong a draft. Such a draft can cause problems during operation, e.g. intensive burning,
high fuel consumption and can also lead to permanent damage of the fireplace insert.
The minimum effective height of the chimney for exhaust gas from the insert is 5m.